A.1.4 Operation/Storage
The UPS system contains no user-serviceable parts. If the battery service life (1~2
years at 25°C ambient temperature) has been exceeded, the batteries must be
replaced. In this case, please contact your dealer.
Be sure to deliver the
spent battery to a
recycling facility or ship it
to your dealer in the
replacement
battery
packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool,
dry location. During storage, recharge the battery in accordance with the following
table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours