The code is show as 27/28 and
the icon
is lighting on LCD
display
and
alarm
is
continuously sounding.
Battery voltage is too
high(27)/low(28) or the
charger is fault.
Contact Atlantis.
The icon
and
is flashing on LCD display and
alarm is sounding every 2
seconds.
UPS is overload.
Remove excess loads
from UPS output.
UPS is overloaded.
Devices connected to
the UPS are fed directly
by the electrical
network via the Bypass.
Remove excess loads
from UPS output.
After repetitive
overloads, the UPS is
locked in the Bypass
mode. Connected
devices are fed directly
by the mains.
Remove excess loads
from UPS output first.
Then shut down the
UPS and restart it.
The code is show as 43 and the
icon
is lighting on LCD
display
and
alarm
is
continuously sounding.
The UPS shut down
automatically because
of overload at the UPS
output.
Remove excess loads
from UPS output and
restart it.
Fault code is shown as 14 and
the icon
is lighting
on LCD display and alarm is
continuously sounding.
The UPS shut down
automatically because
short circuit occurs on
the UPS output.
Check output wiring
and
if connected
devices are in short
circuit status.
Fault code is shown as 1, 2, 3, 4
11, 12, 13, 41 on LCD display
and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still
supplied, but directly
from AC power via
bypass.
Contact Atlantis.
Summary of Contents for A03-OP1001-RC
Page 1: ......
Page 5: ...5 A03 OPX001 RC_MX01 rel 19 0 2 2020...
Page 42: ...ITA 42 Sostituzione Batterie Battery Replacement Suono ogni 2 secondi...
Page 68: ...ENG 68 Step 3 Put the front panel back to the unit Rack Mount Installation Step 1 Step 2...
Page 69: ...ENG 69 Tower Installation Step 1 Step 2...
Page 76: ...ENG 76 EE EEprom error FA FAN BR Battery Replacement RAC Rack display TOE Tower display...
Page 98: ...ENG 98...
Page 100: ...ENG 100...
Page 107: ...Atlantis via C Chiesa 21 Pogliano Milanese MI 20010 Italy info atlantis land com...