Clear 4: Hydraulic Unit Heat exchanger thermistor error
LED
Hydraulic Unit
Outdoor Unit
Green
Red
ÀDVKHV
ÀDVK
ÀDVKHV
Probable causes:
Misconnection.
Sensor failure.
Interface PCB failure.
Check:
Clear 4:
1. Check connection interface PCB and Heat pump regulator PCB:
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Check resistance value:
3 pin of CN22 – M < 10
OK
3. Replace interface PCB:
If check point 1 and 2 do not improve the symptom, replace Interface PCB.
OK
Maintenance document "1546 - EN"
Outoor unit - excellia (duo)
WOYGxxxLCT_WOYKxxxLCT
- 7 -