Clear 8: Heat-exchange thermistor (outlet) error
LED
Hydraulic Unit
Outdoor Unit
Green
Red
ÀDVKHV
ÀDVKHV
ÀDVKHV
Probable causes:
Misconnection.
Sensor fault.
Main PCB failure
Check:
Clear 8:
1. Check the sensor connection:
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistancer value
Temperature (°C)
-10
-5
0
10
15
20
25
30
Resistance (k
)
27,5 20,9 16,1 12,4 9,73 7,67
6,1 3,95
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC5.0V)
- If there is no voltage, replace Main PCB.
OK
OK
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)
Maintenance document "1546 - EN"
Outoor unit - excellia (duo)
WOYGxxxLCT_WOYKxxxLCT
- 10 -