2.2.2 Outdoor unit does not defrost
Is condensation drain properly discharged (outdoor
unit directly on the ground)?
Are the auxiliaries powered?
In boiler backup mode, is the boiler authorized?
In very cold areas, a fusing resistance value is
recommended.
- Is the installation regularly subject to micro-
outages of power (frequent outages on the
mains power system may also cause defrosting
problems)?
- Is there a peak day clearing (EJP) outage on the
installation?
Does the heat pump regularly switch to high pressure
safety mode?
If this occurs at low temperatures (< 5 °C), we
recommend checking that the water pump is operating
properly.
Is the charge correct (refer to the temperature/pressure
curve)?
,QVXI¿FLHQWFKDUJLQJZLOOUHVXOWLQIUHTXHQWLFLQJ
- Overcharging will result in frequently switching
to HP safety mode.
(If you still have doubts as to the charge, perform the
charging with an electronic scale).
Outdoor unit defrosting is controlled by the exchanger
sensor and the controller board.
If the defrost sensor is not iced up while the rest of the
exchanger is, then:
- Move the sensor between the exchanger blades
to a place where the exchanger is iced up.
- If all these points have been checked, replace
the outdoor controller board.
Note:
Outdoor unit defrosting is controlled by the exchanger
sensor and the controller board. If no frosting is observed
and no anomaly is otherwise noted, the sensor and
board must be inspected and the faulty part will have
to be replaced.
'HIURVWLQJ
D 'HIURVWEHJLQQLQJFRQGLWLRQV
Defrost beginning conditions
62’ < t < 240’
Start of heat mode
(Compressor ON)
Cumulative compressor operating time
Defrost
(No defrost for 10 min)
1
st
defrost
Subsequent defrosts
240’ < t
17’ < t < 62’
240’ < t
35’ < t < 240’
O Exch T
-9°C
O Exch T
-5°C
O Exch T
-3°C
O Exch T
-10°C
O Exch T
-3°C
OT – O Exch T >5°C
O Exch T : outdoor unit exchanger temperature
OT : outdoor temperature
t : Cumulative compressor operating time
Maintenance document "1546 - EN"
Outoor unit - excellia (duo)
WOYGxxxLCT_WOYKxxxLCT
- 35 -