Atkinson Electronics GSCM-MINI Manual Download Page 8

www.atkinsonelectronics.com 

             Circuit Board Division 

800.261.3602 

Revised 11/2020

 

GSCM-mini-d Relay Option 3                                 Ignition and Crank Starting Sequence 

 

The configuration terminal 6 has been connected to B+ (terminal 3), configuring the GSCM-mini-d for ignition/crank start 

sequence. The GSCM-mini is then powered by connecting B+ (+12 VDC) to terminal 2. The start LED turns on for 5 seconds 

while the GSCM-mini initializes with option #3 ignition/crank starting sequence then begins blinking the start LED once every 5 

seconds . The generator starting sequence is as follows: 

 

1.

 

The start LED blinks once every 5 seconds to indicate that the GSCM-mini is in a ready mode. When a manual signal is 
received, the start LED lights continuously. After a 2 second delay, K2 relay energizes and remains energized until the 
start signal is either removed or the generator fails to start after 3 attempts. K1 relay closes to crank the starter. The 
K1 relay remains closed until either the generator starts or the maximum cranking time period (20 seconds) is 
reached. 

2.

 

If the generator fails to start after the 20 seconds cranking period, K1 relay opens for a resting period of 40 seconds. 
The K1 relay then closes again cranking the starter until the maximum cranking time is reached or the generator 
starts. 

3.

 

If the generator fails to start after 3 cranking attempts with the associated resting periods then K2 relay de-energizes 
and enters its shutdown routine, then the generator Hz LED does a double blink, the fault LED turns ON and the 
GSCM-mini enters the maximum crank lockout condition. This lockout condition remains until the GSCM-mini is reset 
by removing power from terminal 2 (see GSCM-mini wiring diagram page 4) and reconnecting power. The GSCM-mini 
will then clear the lockout condition, and enter ready mode with the start LED blinking every 5 seconds. 

4.

 

When the generator starts, K1 relay immediately opens, stopping the cranking. A valid run condition is determined by 
one of two conditions: A 12V run pilot light signal provided by the generator connected to terminal 8, or by the 
generators AC output frequency exceeding the crank disconnect setting of 45Hz (terminals 9 & 10) and is indicated by 
the run LED being turned ON. 

5.

 

If the generator starts but shuts down after a few seconds due to a fuel problem, etc., the start sequence will revert 
to the ready mode after a 60 second delay. During this delay the start LED will blink rapidly. The GSCM-mini will then 
try to start the generator again in manual mode or after a 10 minute delay period in auto-start mode. 

6.

 

When a run condition is detected, the GSCM-mini turns ON the run LED and open collector transistor output (remote 
run lamp) and after a 60 second generator stabilization period begins monitoring the AC Hz signal for over/under Hz 
condition. 

7.

 

If the generator starts but shuts down after the 60 seconds stabilization period, due to a fuel problem, low oil 
pressure, broken AC Hz or 12V run status wire, the GSCM-mini blinks the generator Hz LED for an under Hz condition, 
after 60 seconds the run LED turns off, K2 relay energizes for 5 seconds, and fault LED turns on and the generator Hz 
LED blinks four times every two seconds. The GSCM-mini enters a fault shutdown lockout condition and must be 
powered down to reset the fault lockout. 

8.

 

The generator continues running until one of the following occurs: The manual start signal is no longer received, the 
auto battery charge voltage or max run time has been reached while running in auto charge mode, an over or under 
Hz condition occurs (if generator Hz shutdown is enabled) or the generator runs out of fuel. 

When the manual start signal is removed, K2 relay de-energizes opening the ignition circuit shutting down the generator. The 
GSCM-mini then monitors the generator AC Hz input to watch for a zero Hz condition before returning to ready mode. If the 
AC signal remains the GSCM-mini’s generator HZ LED turns on indicating AC Hz. Signal still present and will not return to ready 
mode until the AC signal goes to zero. Once it goes to zero the GSCM-mini returns to ready mode.

Summary of Contents for GSCM-MINI

Page 1: ... Module Part GSCM mini d ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 Contact cbdsales atkinsonel com for the proper hookup diagram Please include the generator make model inverter brand battery bank voltage ...

Page 2: ... and optional battery charging thresholds Maximum auto start run time limit 6 hours Remote run and fault indication included ABS epoxy sealed for harsh environment operation Solving your generators 2 to 3 or 4 wire start stop problem Description The GSCM mini d is a micro processor based generator start stop module designed to auto start stop diesel generators that need a 3 or 4 wire connection fr...

Page 3: ...ication Description The GSCM mini d has six indication LEDs The Start LED blinks once every 5 seconds to indicate it is ready for a start signal The LED will blink once every 2 5 seconds to indicate its running in auto start mode On continuously indicates running in manual start mode The Generator Hz LED blinks to indicate over under Hz fault and start failure due to maximum crank attempted A slow...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 11 2020 GSCM mini d Wiring Diagram Example ...

Page 5: ...lay provides a momentary stop signal until the generator AC Hz has dropped to zero For GSCM mini operational sequence details see page 7 option 2 A double pole kill switch wired and installed by the user stops the generator instantly in emergency situations such as a fuel spill One switch pole N C kills power to the GSCM mini opening all relays The other switch pole N O shorts out the magneto for ...

Page 6: ...oes a double blink the fault LED turns on and the GSCM mini enters the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini wiring diagram page 4 This clears the lockout condition and the GSCM mini re enters ready mode with the start LED blinking every 5 second...

Page 7: ...zed A valid run condition is determined by one of two conditions a 12V run status pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned on 4 If the generator starts but shuts down after a few seconds due to a fuel problem etc The GSCM mi...

Page 8: ...on is determined by one of two conditions A 12V run pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned ON 5 If the generator starts but shuts down after a few seconds due to a fuel problem etc the start sequence will revert to the rea...

Page 9: ...blinks during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini monitors the generators output frequency and if it drops below the 55 Hz fixed threshold for 10 seconds the generator shuts down and the generator Hz shutdown LED blinks slowly The generator Hz LED blin...

Page 10: ...y voltage drops below the start threshold voltage 4 The GSCM mini will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown threshold The GSCM mini then returns to ready mode looking for a start command If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down the GS...

Page 11: ...ion and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescent current 10mA Relay current 25mA each Manual Input B 12VDC input on condition Open input off condition Battery Input 0 60VDC Auto Start Stop Threshold 12V System 11 5V 13 8V 24V System 23 0V 27 6V ...

Page 12: ...te switch is turned on the GSCM mini starts the generator After the generator starts and comes up to speed the run LED lights on the GSCM mini and turns on the remote start switch lamp If the generator fails to start or fails while commanded to run the fault LED on the GSCM mini lights along with the remote fault 12VDC lamp Turning off the power to the GSCM mini resets the fault condition and it i...

Page 13: ...ections to connect the GSCM mini d s start and stop pre heat contacts and the AC output makes for an easy installation When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay which energizes the two relays are used to isolate the glow plug circuit from the shut down circuit causing the glow plug to heat After 10 seconds it energizes the K1 relay to sta...

Page 14: ...ators use a positive reference B for their control switch and remote terminal input The generators AC output is used as a run feedback signal to know when the generator has started and when it shutdown When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay to heat the glow plugs After 10 seconds K2 de energizes and K1 energizes to start the generator ...

Page 15: ...s with an additional relay The GSCM mini monitors the generators AC output to know when to disengage the starter and when the generator has shutdown either by command or by fault When a start signal is received the GSCM mini starts the generator after the generator starts and comes up to speed the run LED lights on the mini If the generator fails to start after 3 starting attempts or fails while c...

Page 16: ... from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to ma...

Reviews: