GSCM-mini-d Relay Option 1                                        Momentary Starting Sequence 

 

The GSCM-mini-d accepts Outback’s 2 wire switched 12VDC start/ run signal or a dry contact, like Samlex, Trace and others, to 
produces a 3 or 4 wire start/ stop signal for most gas, diesel, and propane generators. Using the generators remote port and 
remote pilot lamp (PL) signal, if available, can make for a quick and easy instillation. Some inverter style generators, like 
Yamaha and Honda, do not produce an AC output until the generator is up to full speed which may cause the GSCM to over 
crank the starter. Using the PL signal eliminates this issue. The PL signal or 120/240VAC provides feedback telling the GSCM 
when to stop cranking the starter and when the generator has completely shut down. A red connector with a protection diode 
is provided to connect between terminal 8 on the GSCM-mini and pilot lamp wire for applications where the pilot lamp signal 
is positive or high. If the pilot lamp signal is negative or goes low the pilot lamp signal inverter must be used. The generators 
combination switch should be left in the remote position for the GSCM-mini to auto start the generator. The starting 
sequence is as follows: 

1.

 

The start LED blinks once every 5 seconds to indicate that the GSCM-mini-d is in a ready mode. When a manual signal 
is received, the start LED lights continuously. After a 2 second delay, the K2 relay closes for 10 seconds then opens, the 
K1 relay closes to crank the starter and remains closed until either the generator starts or the maximum cranking time 
period of 20 seconds is reached. 

2.

 

If the generator  fails  to start during the 20 seconds cranking period, the K1 relay opens for a resting period  of 40 
seconds. At the end of the period, the K2 relay again energizes for 10 seconds and de-energizes then, K1 relay  closes 
again, cranking the starter until the maximum cranking time is reached or the generator starts. 

3.

 

If the generator fails to start after 3 cranking attempts with the associated resting periods, the K2 relay then closes for 
5 seconds to ensure the generator is not running, the generator Hz LED does a double blink, the fault LED turns on 
and the GSCM-mini enters the maximum crank lockout fault condition. This lockout condition remains until the 
GSCM-mini is reset by removing power from terminal 2, waiting 5 seconds and then reconnecting power (see GSCM-
mini wiring diagram, page 4). This clears the lockout condition, and the GSCM-mini re-enters ready mode with the 
start LED blinking every 5 seconds. 

4.

 

When the generator starts, the K1 relay immediately opens, stopping the cranking. A valid run condition is 
determined by one of two conditions: A 12V run status pilot light signal provided by the generator connected to 
terminal 8, or by generators AC output frequency exceeding the crank disconnect setting of 45Hz (terminals 9 & 10). 
The GSCM-mini indicates that it has received either signal by turning on the run LED. 

5.

 

If the generator starts but shuts down after a few seconds due to a fuel problem, etc., the start sequence will revert 
to the ready mode after a 60 second delay. During this delay the start LED will blink rapidly. The GSCM-mini will then 
try to start the generator again in manual mode or after a 5 minute delay period in auto-start mode. 

6.

 

When a run condition is detected, the GSCM-mini turns on the run LED and transistor output (remote run lamp 
terminal 11). If an AC signal was detected to disconnect the starter, the GSCM-mini will begin a 60 second generator 
stabilization period before it begins monitoring the AC Hz signal for over/under Hz condition, if enabled (terminal 8 is 
grounded). 

7.

 

If the generator starts but shuts down after the 60 seconds stabilization period, due to a fuel problem, low oil 
pressure, broken AC Hz or 12V run status wire, the GSCM-mini blinks the generator Hz LED for an under Hz condition, 
after 60 seconds the run LED turns off, K2 relay energizes for 5 seconds, and fault LED turns on and the generator Hz 
LED blinks four times every two seconds. The GSCM-mini enters a fault shutdown lockout condition and must be 
powered down to reset the fault lockout. 

8.

 

If no faults occur, the generator will continue to run until one of the following occurs: The manual start signal is no 
longer received and the auto battery charge voltage or maximum auto run time has been reached, while running in 
auto charge mode over Hz condition, under Hz condition occurs if the generator over/under Hz shutdown is enabled, 
or the generator runs out of fuel. 

Summary of Contents for GSCM-MINI

Page 1: ... Module Part GSCM mini d ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 Contact cbdsales atkinsonel com for the proper hookup diagram Please include the generator make model inverter brand battery bank voltage ...

Page 2: ... and optional battery charging thresholds Maximum auto start run time limit 6 hours Remote run and fault indication included ABS epoxy sealed for harsh environment operation Solving your generators 2 to 3 or 4 wire start stop problem Description The GSCM mini d is a micro processor based generator start stop module designed to auto start stop diesel generators that need a 3 or 4 wire connection fr...

Page 3: ...ication Description The GSCM mini d has six indication LEDs The Start LED blinks once every 5 seconds to indicate it is ready for a start signal The LED will blink once every 2 5 seconds to indicate its running in auto start mode On continuously indicates running in manual start mode The Generator Hz LED blinks to indicate over under Hz fault and start failure due to maximum crank attempted A slow...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 11 2020 GSCM mini d Wiring Diagram Example ...

Page 5: ...lay provides a momentary stop signal until the generator AC Hz has dropped to zero For GSCM mini operational sequence details see page 7 option 2 A double pole kill switch wired and installed by the user stops the generator instantly in emergency situations such as a fuel spill One switch pole N C kills power to the GSCM mini opening all relays The other switch pole N O shorts out the magneto for ...

Page 6: ...oes a double blink the fault LED turns on and the GSCM mini enters the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini wiring diagram page 4 This clears the lockout condition and the GSCM mini re enters ready mode with the start LED blinking every 5 second...

Page 7: ...zed A valid run condition is determined by one of two conditions a 12V run status pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned on 4 If the generator starts but shuts down after a few seconds due to a fuel problem etc The GSCM mi...

Page 8: ...on is determined by one of two conditions A 12V run pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned ON 5 If the generator starts but shuts down after a few seconds due to a fuel problem etc the start sequence will revert to the rea...

Page 9: ...blinks during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini monitors the generators output frequency and if it drops below the 55 Hz fixed threshold for 10 seconds the generator shuts down and the generator Hz shutdown LED blinks slowly The generator Hz LED blin...

Page 10: ...y voltage drops below the start threshold voltage 4 The GSCM mini will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown threshold The GSCM mini then returns to ready mode looking for a start command If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down the GS...

Page 11: ...ion and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescent current 10mA Relay current 25mA each Manual Input B 12VDC input on condition Open input off condition Battery Input 0 60VDC Auto Start Stop Threshold 12V System 11 5V 13 8V 24V System 23 0V 27 6V ...

Page 12: ...te switch is turned on the GSCM mini starts the generator After the generator starts and comes up to speed the run LED lights on the GSCM mini and turns on the remote start switch lamp If the generator fails to start or fails while commanded to run the fault LED on the GSCM mini lights along with the remote fault 12VDC lamp Turning off the power to the GSCM mini resets the fault condition and it i...

Page 13: ...ections to connect the GSCM mini d s start and stop pre heat contacts and the AC output makes for an easy installation When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay which energizes the two relays are used to isolate the glow plug circuit from the shut down circuit causing the glow plug to heat After 10 seconds it energizes the K1 relay to sta...

Page 14: ...ators use a positive reference B for their control switch and remote terminal input The generators AC output is used as a run feedback signal to know when the generator has started and when it shutdown When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay to heat the glow plugs After 10 seconds K2 de energizes and K1 energizes to start the generator ...

Page 15: ...s with an additional relay The GSCM mini monitors the generators AC output to know when to disengage the starter and when the generator has shutdown either by command or by fault When a start signal is received the GSCM mini starts the generator after the generator starts and comes up to speed the run LED lights on the mini If the generator fails to start after 3 starting attempts or fails while c...

Page 16: ... from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to ma...

Reviews: