Three Modes of Relay Operation 

 

There are 3 different options for the GSCM-mini-d’s 
two relay contacts to be configured:

  

Momentary, 

Maintained and Ignition.

 

This is accomplished with an 

optional jumper on terminal 6. 

Momentary Start Contact Option #1:

  

Terminal 6 

has no connection.

 The GSCM-mini defaults to a 

momentary crank operation for those generators 

that use two momentary push button switches to 

start and stop the generator.K2 energizes for 10 

seconds for diesel glow plug operation then, K1 

cranks the Starter. On shutdown, K2 momentarily 

grounds the magneto.  See option 1 for operation 

description.

 

Maintained Start Contact Option #2:

 

Terminal 6 is 

grounded.

 The GSCM-mini changes to a maintained 

start operation for generators that use a maintained 

closed contact to start (K1). The generator is stopped 

by opening K1 and closing K2 contact, momentarily 

grounding the magneto. See option 2 for operation 

description. 

Ignition Key Switch Start Contact Option #3:

 

Terminal 6 is connected to B+ (12VDC).

 The GSCM-

mini simulates an automobile ignition switch, K2 

closes, maintains a closed ignition contact for the 

generator to run and K1 closes momentarily to crank 

the starter motor and de-energizes when the start 

signal is removed. The K1 relay operates in a 

momentary crank configuration. See option 3 for 

operation description. 

 

If adjustability is required then 
refer to the GSCM full function 

control module. 

 

 

 

LED Indication Description 

 

The GSCM-mini-d has six indication LEDs.   

The

 

Start LED

 blinks once every 5 seconds to indicate it is 

ready for a start signal. The LED will blink once every 2.5 

seconds to indicate its running in auto start mode. On 

continuously indicates running in manual start mode.  

The Generator Hz LED

 blinks to indicate over/under Hz fault 

and start failure due to maximum crank attempted. A slow 

blink indicates an under Hz condition while a fast blink 

indicates an over Hz condition if pin 8 is grounded. On 

continuously indicates AC present in a non-run condition. A 

double blink indicates a start failure condition. Four blinks 

indicates generator shut down due to its own fault condition 

or lack of fuel.  

The Run LED

, On continuously indicates a valid run signal from 

the generator.   

The Fault LED

, On indicates a fault condition has occurred and 

GSCM-mini is in lockout and must be reset.   

The K1 and K2 LEDs

 indicate the relay status. 

Operational Thresholds 

 

GSCM-mini-d’s fixed operational thresholds:  

 

Crank delay:   

 

 

 5 seconds 

Maximum crank:   

 

 20 seconds 

AC crank disconnect:   

 45Hz 

DC crank disconnect:   

 Voltage greater than 9VDC 

Under speed shutdown: 

 55Hz 

Over speed shutdown: 

 65Hz 

Max auto start run time: 

6 Hours 

Manual start run time: 

Indefinitely 

Auto start/stop thresholds:  Start 

 Stop 

12V system 

    11.5V    13.8V     standard 

    24V system 

   23.0V    27.6V     auto selects 

    48V system 

    46.0V    55.2V     auto selects 

Relay configuration: 

       Open input = momentary crank 

(Terminal 6)   

             Grounded input = maintained crank 

 

 

 

 

            B+ (12VDC) input = ignition & crank 

Fault detection:   

 

Start failure (3 attempts)  

 

Generator stops due to its own fault condition 

 
Fault detection if pin 8 is grounded: 

        

 

        Over Hz condition (10 seconds) 
 

Under Hz condition (10 seconds) 

 

Summary of Contents for GSCM-MINI

Page 1: ... Module Part GSCM mini d ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 Contact cbdsales atkinsonel com for the proper hookup diagram Please include the generator make model inverter brand battery bank voltage ...

Page 2: ... and optional battery charging thresholds Maximum auto start run time limit 6 hours Remote run and fault indication included ABS epoxy sealed for harsh environment operation Solving your generators 2 to 3 or 4 wire start stop problem Description The GSCM mini d is a micro processor based generator start stop module designed to auto start stop diesel generators that need a 3 or 4 wire connection fr...

Page 3: ...ication Description The GSCM mini d has six indication LEDs The Start LED blinks once every 5 seconds to indicate it is ready for a start signal The LED will blink once every 2 5 seconds to indicate its running in auto start mode On continuously indicates running in manual start mode The Generator Hz LED blinks to indicate over under Hz fault and start failure due to maximum crank attempted A slow...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 11 2020 GSCM mini d Wiring Diagram Example ...

Page 5: ...lay provides a momentary stop signal until the generator AC Hz has dropped to zero For GSCM mini operational sequence details see page 7 option 2 A double pole kill switch wired and installed by the user stops the generator instantly in emergency situations such as a fuel spill One switch pole N C kills power to the GSCM mini opening all relays The other switch pole N O shorts out the magneto for ...

Page 6: ...oes a double blink the fault LED turns on and the GSCM mini enters the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini wiring diagram page 4 This clears the lockout condition and the GSCM mini re enters ready mode with the start LED blinking every 5 second...

Page 7: ...zed A valid run condition is determined by one of two conditions a 12V run status pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned on 4 If the generator starts but shuts down after a few seconds due to a fuel problem etc The GSCM mi...

Page 8: ...on is determined by one of two conditions A 12V run pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned ON 5 If the generator starts but shuts down after a few seconds due to a fuel problem etc the start sequence will revert to the rea...

Page 9: ...blinks during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini monitors the generators output frequency and if it drops below the 55 Hz fixed threshold for 10 seconds the generator shuts down and the generator Hz shutdown LED blinks slowly The generator Hz LED blin...

Page 10: ...y voltage drops below the start threshold voltage 4 The GSCM mini will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown threshold The GSCM mini then returns to ready mode looking for a start command If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down the GS...

Page 11: ...ion and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescent current 10mA Relay current 25mA each Manual Input B 12VDC input on condition Open input off condition Battery Input 0 60VDC Auto Start Stop Threshold 12V System 11 5V 13 8V 24V System 23 0V 27 6V ...

Page 12: ...te switch is turned on the GSCM mini starts the generator After the generator starts and comes up to speed the run LED lights on the GSCM mini and turns on the remote start switch lamp If the generator fails to start or fails while commanded to run the fault LED on the GSCM mini lights along with the remote fault 12VDC lamp Turning off the power to the GSCM mini resets the fault condition and it i...

Page 13: ...ections to connect the GSCM mini d s start and stop pre heat contacts and the AC output makes for an easy installation When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay which energizes the two relays are used to isolate the glow plug circuit from the shut down circuit causing the glow plug to heat After 10 seconds it energizes the K1 relay to sta...

Page 14: ...ators use a positive reference B for their control switch and remote terminal input The generators AC output is used as a run feedback signal to know when the generator has started and when it shutdown When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay to heat the glow plugs After 10 seconds K2 de energizes and K1 energizes to start the generator ...

Page 15: ...s with an additional relay The GSCM mini monitors the generators AC output to know when to disengage the starter and when the generator has shutdown either by command or by fault When a start signal is received the GSCM mini starts the generator after the generator starts and comes up to speed the run LED lights on the mini If the generator fails to start after 3 starting attempts or fails while c...

Page 16: ... from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to ma...

Reviews: