MetriNet Ethernet/IP Communications Manual
23
O&M Manual
Rev-A (6/19)
the same “window,” which can provide added security for any changes by
utilizing the user lock codes on the MetriNet if desired.
Figure 10 –Output Assembly Object Command Example with EIP_Tool
Once this message is sent, the S1 delay setting will be updated to 2.0 on the
MetriNet.
The special codes for writing individual registers in the MetriNet come from
specific Modbus register locations in the unit.
Snsr
1
Reg
Snsr
2
Reg
Snsr
3
Reg
Snsr
4
Reg
Snsr
5
Reg
Snsr
6
Reg
Snsr
7
Reg
Snsr
8
Reg
Sensor
Data
Data Format
42003 42021 42039 42057 42075 42093 42111 42129 Delay
10=1.0min
42004 42022 42040 42058 42076 42094 42112 42130
1
Alarm A
(sensor
dependent)
42005 42023 42041 42059 42077 42095 42113 42131
1
Alarm B
(sensor
dependent)
42006 42024 42042 42060 42078 42096 42114 42132 Slp
Alarm
80=80%
42007 42025 42043 42061 42079 42097 42115 42133 Tmr Limit
90=90 days
42008 42026 42044 42062 42080 42098 42116 42134
1
,2
VoutHI
(sensor
dependent)
42009 42027 42045 42063 42081 42099 42117 42135
1,2
VoutLO (sensor
dependent)
42010 42028 42046 42064 42082 42100 42118 42136 TcMode
0 = F, 1 = C
42011 42029 42047 42065 42083 42101 42119 42137
3
Tag1
0x70,0x48=”p”,”H”
42012 42030 42048 42066 42084 42102 42120 42138
3
Tag2
…
42013 42031 42049 42067 42085 42103 42121 42139
3
Tag3
…
42014 42032 42050 42068 42086 42104 42122 42140
3
Tag4
…
42015 42033 42051 42069 42087 42105 42123 42141
3
Tag5
…
42016 42034 42052 42070 42088 42106 42124 42142
3
Tag6
…
42017 42035 42053 42071 42089 42107 42125 42143
3
Tag7
…
42018 42036 42054 42072 42090 42108 42126 42144
3
Tag8
…