SECTION 7 CALIBRATION
WARNING: These adjustments are factory set and should only be changed by a
qualified person using calibrated equipment. Adjustment is not necessary during
the life of these controllers.
7.1
Zero (-cL-) and Span (cH) Calibration
1.
2.
3.
4.
5.
Unlock access to the calibration constants by entering the unlock
number (14) into location 9 (-cd-).
Use a tempemture calibmtor with a range appropriate for the unit to be
calibrated. Set in the value for low scale calibration, e.g. (1 % of range).
Step to -cL- (calibmte low [ZERO]) using tie index key on the 6075.
press the up/down keys on the 6075 until both instruments agree
press the ‘ENTER’ key.
Set in a value on the calibrator equivalent to the high-end capability of
the unit under test e.g. (95% of range).
Step to -cH- (calibrate high [SPAN]) using the INDEX key.
Press the up/down keys on the 6075 until both instruments agree.
Press the "ENTER" key.
Repeat steps2 thru 7 until readings agree. Some interaction between
Zero(-cL-) and Span (-cH-) calibration usually occurs
Lock out configumtion access, if desired, and return to set point by
pressing "SET POINT" key.
NOTE: Pressing index continuously selects -cH- or -cL- (Span and Zero) in
the calibrate mode to faciliite testing. Exit this mode by pressing the ‘SET
POINT" key.
33
6.
7.
8.
9.
Summary of Contents for 6075 series
Page 1: ...SERIES 6075 TEMPERATURE CONTROLLERS WITH AUTO TUNING PID AND PLUG IN COMPUTER INTERFACE...
Page 6: ......
Page 7: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 13: ......
Page 17: ......
Page 21: ......
Page 27: ......
Page 29: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......