5.2
Basic Series 6075 Setup
1.
The 6075 has dual-input ranges which allow selection of one of two
ranges and T/C types, by simply moving the position of the internal
jumper.
To set unit to proper range, remove unit from case and position jumper on
top board. Front position is range A, rear position is range B, grouped s
offered.
A = 01F No Jumper = 26F A = 33F A = 22F No Jumper = 22C
B = 02F B = 32F B = 26C
Consult Serial Tag for actual range and sensor type ordered. Ranges
are defined in Section 1.3, Model Number Identification.
The Series 6075 is shipped from the factory with the following settings:
SP = 100 CG = 30 Id = 01
A1 = 105 CC = 05 (F=00) bd = 02
A2 = 95 cd = 08 cL = Range dependent
rt = 00 AT = 00 cH = Range dependent
HG = 30 cF = 08 (05 for ºC ranges)
HC = 05 (F=00) ct = 00
14