5
Pre-Wire Setup
Note:
Do not use a screwdriver or other
metal object to pry open the case. Only
slight hand pressure is required.
Note:
The 1ZC communicates
according to the RS-485 standard. This
allows for up to 32 devices to be on a
single twisted pair. Use of a signal
repeater will allow more devices to
be addressed.
Before wiring the 1ZC controller, the
network address of each unit must be set
using a binary DIP switch located on the
controller’s circuit board.
DO NOT
ATTEMPT TO CONNECT POWER
WIRING BEFORE COMPLETING
THIS STEP.
Pull apart case sides to disengage locking
tabs while pulling out the black bezel.
Locate the 8-position DIP switch and
assign a unique network ID to each
controller by setting the DIP switch to
the appropriate binary number (Fig.1).
Valid network IDs are 1 to 254. (Zero
and 255 may not be used.)
Switch Number
Hex
Decimal
Address Descriptions
1
2
3
4
5
6
7
8
Equivalent Equivalent
Factory Use ONLY
OFF
OFF OFF
OFF OFF OFF OFF OFF
00h
0
First usable address
ON
OFF OFF
OFF OFF OFF OFF OFF
01h
1
Second usable address
OFF
ON
OFF
OFF OFF OFF OFF OFF
02h
2
Third usable address
ON
ON
OFF
OFF OFF OFF OFF OFF
03h
3
Fourth usable address
OFF
OFF
ON
OFF OFF OFF OFF OFF
04h
4
Last usable address
OFF
ON
ON
ON
ON
ON
ON
ON
FEh
254
Default communications
ON
ON
ON
ON
ON
ON
ON
ON
FFh
255
settings: 2400 Baud; 8, n, 1
1ZC DIP Switch Settings
Figure 1. Binary Code DIP Switch for
setting network IDs for each controller.
Series 1ZC Communicating Sub-Panel Temperature Controller
When reassigning a
network ID after Input/
Output/Power wiring is
attached, disconnect wiring
connector, then remove board as noted
earlier.
NEVER ATTEMPT TO REMOVE
CIRCUIT BOARD WITH POWER WIRING
ATTACHED. HAZARDOUS VOLTAGE IS
PRESENT ON CIRCUIT BOARD.