2
Option #20: Dual Open Collectors, NPN, Isolated
with Clamping Diode
Dual Open
Collector Alarms
Option Description:
Dual open collectors, NPN, isolated, with clamping
diode
Recommended operating conditions:
Supply Voltage
Pins 13 & 14; 200 working Vdc max. (Never exceed
300 Vdc)
Collector Current
50 mA max.
Specifications:
Saturation Voltage
0.3 Vdc min.
1.2 V max.
Collector-Emitter
Breakdown
300 V min.
Isolation
Isolation 300 volts ac/dc output-to-output or output-
to-controller