7
Contact/Digital
Input with Alarm
Option Description:
Dual function board (functions unrelated)
a. Output alarm is energized when either A1
or A2 is active.
b. Digital input controls Remote Standby, Ramp-Soak
Run/Hold, OR Second Setpoint Select.
Option 40: Active when switch closed.
Option 41: Active when switch open.
Option 42: Active when 5 V input present
Load Limits:
Max. Load Current:
1 A rms
Min. Load Current:
0.5 mA rms
Power Factor Range:
0.2 to 1.0 (can drive small motors, solenoids, valves,
and contactors)
Max. Surge Current,
Non-Repeating for
1 second:
7.5 A
Max. I
2
T for fusing (0.01 sec):
4.5 amp-squared secs (1A - ABC1
typical fuse)
Contact/Digital
Input with Alarm
Options #40, #41, #42: Contact/Digital Input with
Alarm
Input Option Menu