Technical specification

Power supply

• V

CC

• Power consumption

15 – 50 V   
3 W

Environment
• Ambient temperatures
• Humidity

• Pressure

-20 – 40

O

C

10 – 90% long term

0 – 99% short term
1013 ± 10% hPa

IP

IP 65

Two-state outputs parameters

• Relay

Floating contacts, NO/NC: 24 V   / 0.1 A, 
Not protected against overloading 

Control output for the shutoff valve

• Range of load resistance /power

• Guaranteed limit of the shutoff voltage
• Maximum resistance of the power supply line
• Duration of the shutoff pulse 

PW-121-L-X: ≥ 4 Ω / ≤ 36 W
PW-121-H-X: ≥ 2 Ω / ≤ 72 W

10.5 V
See Section 7.2.1
0.5 s

Parameters of the input for an external alarm signal Connection via a potential-free contact 

Inactive for resistance below 10 Ω
Active for resistance above 3300 Ω
Minimum duration of the switchover pulse  > 1s

Digital communication parameters 
• Teta BUS port

• Communication protocol

Teta BUS

Integrated signalling equipment (visual)

LED controls

Protection class

III

Dimension

See Figure  2

Cable glands
• Cable diameter range

5 – 10 mm

Cross-section of wires for clamping terminals
• Relay outputs, DI, TETA

• Power voltage

0.08 – 2.5 mm

(use sleeves 2 x 1 mm

2

 or 2 x 0,75 mm

2  

for twin

conductors)
1 – 4 mm

(use sleeves 2 x 1.5 mm

2

  or 2 x 1 mm

2

  for twin

conductors)

Enclosure material

ABS

Weight

PW-121-L-X: 1.0 kg
PW-121-H-X: 2.5 kg

Lifetime of consumables

See Table 9, Section 9

Mounting

4 screw holes 4 mm, hole spacing:
PW-121-L-X: 160 x 110 mm
PW-121-H-X: 110 x 110 mm

Table 8: Technical specification

s. 14|15

User Manual: POD-067-ENG R01

Summary of Contents for Control V

Page 1: ...POD 067 ENG R01 User Manual Valve Controller Control V Product code PW 121 X...

Page 2: ...ring Detection and Reduction of gas hazards We invite you to familiarize yourself with our offer on www atestgaz pl Atest Gaz A M Pachole sp j ul Spokojna 3 44 109 Gliwice Poland tel 48 32 238 87 94 f...

Page 3: ...nts during the entire lifetime of the product Use of unauthorized spare parts different from the ones listed in Table 9 is strictly forbidden How to use this manual The following symbols of optical in...

Page 4: ...ce status 8 Table 4 Meaning of LED indicators in the battery status 8 Table 5 Meaning of LED indicators in the valve status 9 Table 6 Description of TEST button 9 Table 7 Selection of cables for conne...

Page 5: ...f the controller is subjected to continuous monitoring of its operability and its key parameters where such items as continuity of the line for valve control its resistance charging status of the embe...

Page 6: ...roper way Before painting the floors make sure the device is secured 3 Description of the construction Product code Dimensions mm A B C D E PW 121 L X 125 110 125 110 75 PW 121 H X 175 160 125 110 100...

Page 7: ...2 Electric interface description 4 1 1 Power supply port for a valve to be controlled The output port designed to supply a shutoff valve The port is monitored resistance of the output line is continuo...

Page 8: ...igital communication with other devices of the Teta series PLN Power Line Networking 5 User interface Figure 4 Front panel 5 1 Device status Indicator Status colour Information green Regular operation...

Page 9: ...ection 7 5 1 Indicator Status colour Information No need to test the valve green Slow blinking of the LED indicator test of the valve is needed see details in Section 7 5 1 green Test of the valve is...

Page 10: ...ll with cable glands downwards where the mounting position is shown in 2 The location of the device should be easily accessible to operating personnel but access of unauthorized persons should be rest...

Page 11: ...f cable cores mm2 Cross section of a cable parallel connection of cores mm2 Maximum length of the cable for valves with power 72 W m Maximum length of the cable for valves with power 36 W m 1 5 2x1 0...

Page 12: ...ted to the controller On the contrary moving the switch to the OFF position makes the controller to close the shutoff valve connected to the valve port when the contacts of the DI port are shorted see...

Page 13: ...e order 7 5 3 Maintenance Except cleaning the external part of the enclosure the device does not require any maintenance The external part of the enclosure should be cleaned by means of a soft cloth m...

Page 14: ...ial free contact Inactive for resistance below 10 Active for resistance above 3300 Minimum duration of the switchover pulse 1s Digital communication parameters Teta BUS port Communication protocol Tet...

Page 15: ...ry 12 V 5 Ah 1 year MW Power MW 5 12 Table 9 List of consumables 10 Product marking Control V Valve Controller PW 121 Valve type L Coil resistance 4 power consumption 36 W H Coil resistance 2 power co...

Page 16: ...certain voltage limits EN 60335 1 2012 in relation to directive 2011 65 EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment EN 50581 2012 other EN 6...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Reviews: