Life cycle
7.1
Transportation
The device should be transported in the same way as new devices of this type. If the original box or another
protection (e.g. corks) is not available, it is necessary to secure the device against shocks, vibrations and
moisture on one's own, using other equivalent methods.
The device can be conveyed under environmental conditions as described in Table 8.
7.2
Installation
The device should be mounted on a flat a vertical wall with cable glands downwards, where the mounting
position is shown in 2. The location of the device should be easily accessible to operating personnel but
access of unauthorized persons should be restricted as much as possible. It is recommended to install the
device at the height that enable easy access to the device.
Combining two or more wires at a single terminal is not allowed if such wires are not
clamped in a common cable ferrule (details see Table 8).
Leaving spare lengths of cables inside the device is not allowed. Bare wires or wires surplus
may lead to a hazard of electric shock or equipment damage.
All cable cores must be terminated inside the device. Leaving unterminated cores is not
allowed.