Maximum quantity of Alpa EcoTerm XT detectors by cable
type
1
Open loop configuration
Cross-section of
a single cable
conductor
[mm
2
]
Alpa EcoTerm XT Gas Detector
System without backup battery supply
(U
IN
= 24 V)
System with backup battery supply
(U
IN(min)
= 20 V)
L1 [m]
L2 [m]
Quantity of detectors
L1 [m]
L2 [m]
Quantity of detectors
1
48
408
13
34
334
11
81
411
12
67
337
10
115
415
11
102
342
9
153
423
10
141
351
8
196
436
9
187
367
7
1,5
47
497
16
49
409
13
79
499
15
82
412
12
113
503
14
117
417
11
148
508
13
155
425
10
187
517
12
198
438
9
229
529
11
248
458
8
2,5
39
669
22
42
552
18
72
672
21
74
554
17
104
674
20
108
557
16
137
677
19
142
562
15
172
682
18
179
569
14
Table 1: Maximum quantity of Alpa EcoTerm XT detectors – open loop configuration
Atest-Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
p. 1/3
Appendix: PU-Z-106-ENG R01
•
Figure 1: Open loop configuration
Control
unit
Detectors installed 30 m apart
Length L2 [m]
Length L1 [m]
Alpa
EcoTerm XT
Alpa
EcoTerm XT
Alpa
EcoTerm XT
L1 – distance T-connector of the first detector from the control unit
L2 – distance T-connector of the last detector from the control unit