www.atestgaz.pl
in case of controlling more powerful circuits and bigger inductive load an additional controlling
contractor should be used, directly controlling the device (e. g. a set of fans),
do not exceed technical data limits shown in table 6.
6.4
The basic configuration relay outputs and digital inputs
Relay
output
Function
Input activation:
Output inactivation:
R1
WARNING
Warning threshold has been exceeded or DI1 or
DI2 activated
The decrease in the measured gas concentrations
below the warning threshold; DI1 and DI2 inactive
R2
ALARM
Alarm threshold has been exceeded or DI1 or DI2
activated
The decrease in the measured gas concentrations
below the alarm threshold; DI1 and DI2 inactive
R3
LATCHED
ALARM
Warning threshold has been exceeded or DI1 or
DI2 activated
The decrease in the measured gas concentrations
below the alarm threshold; DI1 and DI2 inactive
and pressing the CONFIRM / CLEAR key
R4
FAILURE
None of the devices has the FAILURE status
At least one device in the system signals a failure
or no power
Table 3: Relay outputs
Voltage
output
Function
Input activation:
Output inactivation:
OC1
WARNING
Warning threshold has been exceeded or DI1 or
DI2 activated
The decrease in the measured gas concentrations
below the warning threshold; DI1 and DI2 inactive
OC2
ALARM
Alarm threshold has been exceeded
The decrease in the measured gas concentrations
below the alarm threshold; DI1 and DI2 inactive or
pressing the CONFIRM / CLEAR key
*U
ZAS
– voltage on power supply terminal of control unit module (voltage on OC output in activation = U
ZAS
)
Table 4: OC voltage outputs
6.5
Frequency of periodical operations
The device should be subjected to periodic inspection of its technical condition. It is the user's
responsibility. The user is obliged to supervise the installation on the ongoing basis, according to schedule
as below:
Frequency
Description of activities
Daily
Checking the device indications
Once in a quarter
Checking the installation, mechanical defects
Checking operation of the detector (by exposing it to gas)
Table 5: Frequency of periodical operations
These tests are performed by a trained and qualified person. He / she is obliged to immediate notification of
the manufacturer of any observations and suspicions about the status of the device.
s. 12|15
User Manual: POD-006-ENG R03