VI.4 Electric board's terminal
VI.4.1 Power terminal connection 9008 to 9070
GTDHR FIRST / PREMIUM / INFINITE
ENERGY RECOVERY UNIT
MS-CDF-001 A
Ind A
update 01/07/2011
Created by JC
Validated by AR
9 / 36
35
38
29
39
30
40
41
32
42
43
34
44
45
36
31
33
Power terminal and accessories
for fan operations
(on upper DIN rail)
7
15
1
16
2
17
18
4
19
20
6
2
1
22
8
3
5
243
9
24
10
25
26
12
27
28
14
11
13
Control terminal
(on lower DIN rail)
46
37
35
38
29
39
30
40
41
32
42
43
34
44
45
36
31
33
Power terminal and accessories
for fan operations
(on upper DIN rail)
46
37
Name
Termi-
nals
Connection
DEP S
29
30
To be connected on terminals 1 and 3 of the air
flow-rate control
DEP
ressure Switch on Supply Air
fan set at 30Pa (to be noted that safety of the air-
flow rate shall be managed by the pressure trans-
mitter in case of the LOBBY
®
EC, QUATTRO
®
EC,
MAC2
®
EC option. In this case do not connect any-
thing to these terminals).
SUPPLY AND
RETURN AIR
MOTOR
31-32-
33-34-
35-36-
40-41
According to De CARMA
®
size (see chapter VI.5)
DEP S
38
39
To be connected on terminals 1 and 3 of the air
flow-rate control
DEP
ressure Switch on Return Air
fan set at 30Pa (to be noted that safety of the air-
flow rate shall be managed by the pressure trans-
mitter in case of the LOBBY
®
EC, QUATTRO
®
EC,
MAC2
®
EC option. In this case do not connect any-
thing to these terminals).
BE Regulator
(PREMIUM AND
INFINITE BE
only)
42
43
Only for
CARMA
®
PREMIUM BE
and
INFINITE
BE
, connect on terminals 1 and 2 of the
BE regula-
tor.
(see chapter VI.15)
DEP FS
44
45
To be connected on terminals 1 and 3 of the fouling
DEP
ressure switch of the Supply Air Filter. (set at
200Pa)
THS (PREMIUM
AND INFINITE
BE only)
37
46
Only for
CARMA
®
PREMIUM BE
and
INFINITE
BE
, connect on terminals C and 2 of the electric
battery's Safety Thermostat
.
(see chapter VI.15)