VI.17 / Repeater (see chapter VII.3.8 for the configuration)

 

If you would like to have remote control in addition to the display, you must use a repeater. In this case you can move 
the remote control system up to 1 km away. Use a shielded twisted 2-pair cable of BELDEN 8723 type or equivalent to 
connect the repeater to the control housing and a standard cable (2x0.5 min. to 2x1.5 max.) for the 24V. You can con-
nect up to 6 housings to the same repeater. Cannot be linked to a MODBUS communication but can be linked to a LON 
communication.

 

VII / SETTING 

 

VII.1 / Control (on Corrigo or remote control)

 

The monitor has four rows with 20 characters. It is back-lit. This lighting is not permanent but activates when a key is 
pressed. The lighting switches off after a period of inactivity.

 

There are two LEDs on the front panel:

 

 

Alarm LED represented by the bell symbol.

 

 

Write LED represented by the pencil symbol.

 

 

 

Rapid blinking = possibility of changing the value

 

 

 

Slow blinking = a password needs to be entered to change the value

 

 

The Up, Down, Left and Right directional keys are used to navigate inside the menus.

 

  

The Up and Down keys are also used to increase or decrease the value of a parameter when it is accessible  

  

whereas the Left and Right keys are also used to navigate within the same parameter.

 

 

The OK key is used to enter the value and confirm a selection and the C key is used to cancel.

 

 

The alarm key (red) is used to access the fault list.

 

 

The left arrow is also used to exit the alarm menu to return to the main menu

 

 

The cursors show you the possible movements and on which arrows to press.

 

 

GTDHR   FIRST / PREMIUM / INFINITE 

ENERGY RECOVERY UNIT 

 

 

MS-CDF-001 A 

Ind A 

update 01/07/2011  

Created by JC 

Validated by AR 

18 / 36 

 

CORRIGO CARMA 

 

 

REPEATER 

 

 

Connect the wires as follows: 



B

 of the repeater to the B terminal of the CARMA

®

 unit (wire of the shielded cable as given in the diagram below) 



A

 of the repeater to the A terminal of the CARMA

®

 unit (wire of the shielded cable as given in the diagram below) 



N

 of the repeater to the N terminal of the CARMA

®

 unit (shielding of the shielded cable as given in the diagram 

below) 



G

 of the repeater to terminal 7 of the CARMA

® 

unit

  

 



G0

 of the repeater to terminal 8 of the CARMA

® 

unit

 

 

 

 



  



 

Arrows 
(MENU  
directional  
keys) 

Cursor

 

 

      Analogue input:  
      Digital input: 
      Analogue output: 
      Digital output:  

Option of going up

 

 

Option of going down

 

 

Less than 1000m 

10m (cable supplied) 

Summary of Contents for GTDHR FIRST

Page 1: ...GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT OPERATING AND MAINTENANCE INSTRUCTIONS MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 1 36...

Page 2: ...8 36 VI 3 Connection of the probes P 8 36 VI 4 Electric board s terminal P 9 to 11 36 VI 4 1 Power terminal connection 9008 to 9070 P 9 36 VI 4 2 Control terminal connection 9008 to 9070 P 10 and 11...

Page 3: ...3 3 c CARMA MAC2 and QUATTRO EC P 23 36 VII 3 4 Temperature set point modification P 24 36 VII 3 5 CO2 set point modification P 24 36 VII 3 6 Unit start stop or forced LS HS start through the Corrigo...

Page 4: ...ed into the environment I 3 Storing The equipment must be stored in shade in a dry place at a temperature between 20 C and 40 C II INSTALLATION II 1 Handling The units must only be moved in their inst...

Page 5: ...ipe A siphon can only be used for one drainage system Note the si phon must be connected in accordance with Best Practices in order that the condensates are removed as efficiently as possible The heig...

Page 6: ...dry contact NO Supply air temperature management with outdoor compensation air relationship III 5 CARMA MAC2 EC 1 or 2 CONSTANT flow rates as required m3 h Adjustment of 1 or 2 constant flow rates LS...

Page 7: ...by AR 7 36 NEW AIR RETURN AIR VS Supply Air Fan VR Return Air Fan DEP FS Filter Pressure Switch only for new air PT1000 PROBES and Servomotors SSG Supply Air Duct Probe SDG Duct Defrost Probe SEG Exte...

Page 8: ...Agnd 33 and AI4 35 SBD Defrost Battery Probe on Agnd 36 and AI4 37 for INFINITE BE or a 1000 Ohms resistance for FIRST and PRE MIUM GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A...

Page 9: ...ns mitter in case of the LOBBY EC QUATTRO EC MAC2 EC option In this case do not connect any thing to these terminals SUPPLY AND RETURN AIR MOTOR 31 32 33 34 35 36 40 41 According to De CARMA size see...

Page 10: ...ut available if the CARMA unit is associated with the LOBBY EC option for opening the dampers during Night Cooling period see chapter VI 9 DX 2 DO7 24V output available for starting a direct expansion...

Page 11: ...BE PREMIUM BE and INFINITE BE versions the K1 auxiliary contact is factory connected FIRST version if you install an additional BE module to the CARMA unit to be connected to the C and 2 terminals of...

Page 12: ...CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 12 36 CARMA 9008 SUPPLY AIR POWER CONTROL CONTROL GREEN YELLOW BLUE BROWN BLUE YELLOW GREEN YELLOW BLUE BROWN WHITE BROWN SHIELDING GREE...

Page 13: ...INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 13 36 GTDHR 9016 9023 CONTROL POWER SUPPLY AIR POWER CONTROL RETURN AIR RETURN AIR GTDHR 9035 9048 GTD...

Page 14: ...emperature set point the water battery valve will open or the electric battery will start In summer FREE COOLING The Bypass closes when the outside temperature is higher than the inside temperature to...

Page 15: ...n the hot water battery is already installed in the unit The Anti frost Thermo stat is connected However you should wire the 3 way valve For all other versions also connect the THA Anti frost Thermost...

Page 16: ...lectric battery housing follow the diagram as given below VI 15 Heating electric battery CARMA PREMIUM BE and INFINITE BE In PREMIUM BE and INFINITE BE version the electric battery is already installe...

Page 17: ...d INFINITE BC version the defrost battery is already installed in the unit The control is also connected GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created...

Page 18: ...enus The Up and Down keys are also used to increase or decrease the value of a parameter when it is accessible whereas the Left and Right keys are also used to navigate within the same parameter The O...

Page 19: ...to 7 Operating period Vent AS 00 0 Hours Viewing the alarm log use the bottom arrow to scroll the log Alarm report Inputs outputs Analogue inputs AI1 AS Temp supply air AI2 Ext Temp outdoor AI3 Def Te...

Page 20: ...2 OR QUATTRO EC Actual 4178m3 h example Set point 5000m3 h 5 Frequency control AS manual vent Output 1 1 75 5 Output 1 2 50 5 CO2 CARMA DIVA EC OR QUATTRO EC Actual 654ppm example Set point 1000ppm 6...

Page 21: ...y 3 Per 1 12 00 14 00 Per 2 18 00 00 00 Etc up to Sunday and vacations Vacations mm dd up to 24 periods 4 1 01 01 01 01 example 1 January 2 12 25 12 25 example 25 December 1 Time Date Day Setting see...

Page 22: ...d pgr or Reduced speed pgr menu as indicated in chapter VII 2 Once on this menu press the OK key Fill in the desired value Validate by pressing the OK key to go to the next field Use the down arrow to...

Page 23: ...the welcome screen VII 3 3 b CARMA LOBBY EC 5 chapter VII 2 You can change the constant pressure of your unit for each fan to set your flow rates To set your initial HS flow rate force the system int...

Page 24: ...t changeable If you increase or decrease a value all the others should be increased by the same value to comply with this air relationship principle Validate by pressing the OK key to go to the next f...

Page 25: ...to the Configuration menu For this you should get the Service level access rights Follow the procedure given below Enter the code 2222 with the help of the directional keys and then validate with the...

Page 26: ...ll be able to enable the MODBUS and modify the PLA and ELA addresses 1 Activation of MODBUS Inactive as standard 2 PLA ELA address addressing of the regulator as standard PLA 254 ELA 254 Access rights...

Page 27: ...on VII 3 8 c LON Communication if CORRIGO with LON option No parameter is to be set in the Corrigo you will find the required files at the following address ftp ftpserver regin se Communication 20vari...

Page 28: ...d AR vent fault Return air fan not working A 30s 120s for LOBBY MAC2 QUAT TRO EC The pressure switch is wrongly connected the pressure switch should be set at 30Pa The motor is not working The pressur...

Page 29: ...rror Defrost temperature probe error C 5s The defrost temperature probe SDG is not working or is wrongly wired see chapter V Supp temp regulator error Defrost battery probe error C 5s The defrost batt...

Page 30: ...is described below A condenser is used to back up the memory and to operate the clock for about 10 minutes after the current has been dut If the battery change operation takes less than 10 minutes the...

Page 31: ...transmitted to the external items unit and regulation Check the electrical connections every year Filtration do not damage the filtering media Classification Filtration efficiency EUROVENT Reference W...

Page 32: ...GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 32 36 X NOTES Date Observations...

Page 33: ...setting LS Factory setting HS Factory setting LS 90 80 40 MIN GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 33 36 Flow rate m3 h...

Page 34: ...setting HS Factory Setting LS 80 100 40 MIN GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 34 36 Flow rate m3 h Static pressure p...

Page 35: ...ing HS Factory Setting LS Factory Setting HS Factory Setting LS GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 35 36 Flow rate m3...

Page 36: ...FINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 36 36 http www airtradecentre com 90 70 60 50 40 80 Factory setting Factory setting 100 Flow rate m3 h St...

Reviews: