Applied Thermal Control Ltd
39 Hayhill Industrial Estate
Barrow-upon-Soar, Loughborough
LE12 8LD, United Kingdom
+44 (0) 1530 839 998
[email protected]
[email protected]
Installation, Operation & Service Manual
EcoMini (EMxxn)
DOCUMENT DETAILS
Date 28/AUG/2020
Author(s) MJH
Page 3 / 5
Revision 1
PRODUCT SPECIFICATIONS
Attribute
Unit
Value
Pending data collection
Power consumption curves
Cooling capacity curves
Pump performance curves
Dimensions (W*D*H)
mm
180*435*380
inch
7.1*17.1*15
Weight
kg
20
lbs.
44.1
Heat transfer fluid volume
mL
650
USGal
0.172
Cooling capacity
(T
ambient
+20°C / +68°F)
(T
setpoint
+20°C / +68°F)
W
500
BTU/h
1706
RT
0.142
Standard temp. range °C
+4 to +35
Optional temp. range °C
-10 to +65
Power supply requirement
VAC
100-240
Hz
50/60
A
1@240VAC
2@115VAC
Sound pressure level dB
64
Auto-diagnostic functions
Undertemperature cutout
Overcurrent cutout
Refrigeration overpressure cutout
Display
Process temperature
Compressor active/inactive
Fluid fittings (standard) Pushfit 12mm
Fluid fittings (option) Valved QR
Tool-less access No
Undertemperature
protection
Via display setup
Overtemperature
protection
Hardware limited
Compressor overload
protection
Via PCB function
Overcurrent protection Fused, 2* T6.3A H250V
Rated duty cycle Continuous
1
st
party approvals CE
3
rd
party approvals
UL61010-1
CAN/CSA-C22.2
FCC CFR47 Part 15 Subpart B
IEC61000-6-4:2007 +A1:2011
IEC61000-6-2:2005
IEC61000-3-2:2014
IEC61000-3-3:2013
Compatible heat transfer
fluids
DI water
Propylene glycol Hexid A4, A6
Opening section EMPC3