36
Flue gas system
Collective flue gas outlet underpressure
Diameter and venting lengths of the flue gas outlet/air supply:
Closed system, with under
-
pressure (calculated with thermal draft) under atmospheric ircumstances.
Closed system, underpressure, parallel
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2
-
5
h = 5
-
9
h = 9
-
13
h = 13
-
17
114
-
240
240
220
220
220
240
-
360
330
300
290
270
360
-
480
390
370
350
330
480
-
600
460
410
390
380
600
-
720
500
460
440
420
720
-
840
550
500
470
460
840
-
960
600
540
510
490