13
Technical description
Technical data
ErP data
XL
-
F
75
105
Permit
CE0063CT3449
Category
GB: II2H3P
Heat exchanger type
iConXL1
iConXL2
Output
G20
Full load
80/60°C
kW
65,4
90,2
40/30°C
kW
72,0
99,0
Low load
80/60°C
kW
14,6
18,1
40/30°C
kW
16,1
19,9
G31
Full load
80/60°C
kW
65,4
90,2
40/30°C
kW
72,0
99,0
Low load
80/60°C
kW
23,2
34,3
40/30°C
kW
25,6
37,7
Input
G20
Full load
kW
66,7
92,3
Low load
kW
14,9
18,5
G31
Full load
kW
66,7
92,3
Low load
kW
23,6
35,0
Gas consumption
G20
Full load
m3/h
7,1
9,8
Low load
m3/h
1,6
2,0
G31
Full load
kg/h
5,5
7,6
Low load
kg/h
1,92
2,84
Boiler efficiency
Full load
80/60°C
%
98,0
97,7
Full load
40/30°C
%
108,0
107,3
Low load
80/60°C
%
98,3
97,9
Low load
40/30°C
%
108,4
107,6
Gas type
Natural gas or Gas propane
CO2 natural gas
min./max
Vol. %
8,7 / 9,3
CO2 propane gas
min./max
Vol. %
10,2 / 10,8
O2 natural gas
min./max
Vol. %
5,3 / 4,3
NOx class
6
6
Max. flue gas temperature
80/60°C
61
71
Mass flow of flue gas
kg/h
120
166
Overpressure at boiler output
max
Pa
156
243
Water content
max
l
9,3
13,9
Weight
kg
73
80
Gas flow pressure
-
standard
mbar
20
Gas flow
-
pressure min./max.
mbar
17 / 25
Water pressure
min./max
bar
0,7 / 6
Voltage/frequency
min./max
Volt/Hz
230 / 50
Max. power consumption
W
137
120
Power consumption part load
W
45
95
Power consumption stand by
W
5
5
Width / depth / height
mm
530/595/1100
530/675/1100
Gas external thread
R
Rp 1.1/4"
Rp 1.1/4"
Flow/return external thread
R
Rp 2"
Rp 2"
Flue gas connection PPS
Diameter
DN
100
100
Outdoor air connection
Internal
in mm
100
100
Condensate connection PVC
External
in mm
35,5
35,5
ErP data according to 813/2013/EU
70
100
Seasonal room
-
heating energy efficiency class
A
Nominal heat output
Pn (kW)
64
88
Seasonal room
-
heating energy efficiency class
η
s (%)
93
93
Annual energy consumption
QHE (GJ)
199
272
Noise output level, inside
LWA (dB)
65
60
At rated heat output and high
-
temp regime 80/60°C
P4 (kW)
65,3
90,2
At 30 % of rated heat output and low
-
temp regime 36/30°C
P1 (kW)
21,8
30,2
At rated heat output and high
-
temp regime (GCV)
η4 (%)
88,2
88,0
At 30 % of rated heat output and low
-
temp regime (GCV)
η1 (%)
98,3
98,2
At full load
elmax (kW)
0,137
0,120
At part load
elmin (kW)
0,045
0,095
In standby mode
Psb (kW)
0,005
0,005
Standby heat loss
Pstby (kw)
0,086
0,075
Summary of Contents for XL-F 105
Page 2: ...2...
Page 25: ...25 Technical description Declaration of conformity...
Page 41: ...41 Boiler installation Electrical connection...
Page 42: ...42 Boiler installation Electrical connection...
Page 49: ...49 Boiler installation Electrical connection Cascade control...
Page 71: ...71 Accessories Hydraulics Single boiler Dimensional sketch for Back pack PHE kits...