35
Flue gas system
Collective flue gas outlet underpressure
Diameter and venting lengths of the flue gas outlet/air supply:
Open system, with underpressure (calculated with thermal draft) under atmospheric circumstances.
NOTE!
1. IPX0D at flue category B23 and B33
Open system, underpressure
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2
-
5
h = 5
-
9
h = 9
-
13
h = 13
-
17
114
-
240
210
200
190
190
240
-
360
300
270
260
250
360
-
480
360
330
310
300
480
-
600
440
380
360
340
600
-
720
470
420
400
380
720
-
840
550
470
430
410
840
-
960
600
510
470
440