Pitch Pipe Back
Toward Air Receiver
Oil and Water Extractor should be at least 25 ft. from the compressor.
Further if possible.
Oil and Water
Extractor
PIPE SIZE, I.D. (Inches)
04
1/2" THOR Impact Wrench
1894
SUGGESTED AIR LINE CONNECTION
The oil and water extractor should not be mounted on or near the air compressor.
The temperature of air is greatly increased during compression. As the air cools down to room
temperature, in the air line, on its way to the Air Power Tool, the moisture contained in it condenses.
Thus, for maximum effectiveness, the oil and water extractor should be mounted at some point in the
air supply system where the temperature of the compressed air in the line is likely to be lowest.
Air lines must be properly drained daily. Each low point in an air line acts as a water trap. Such points
should be fitted with an easily accessible drain. See diagram below. Pitch all air lines back towards the
compressor so that condensed moisture will flow back into the air receiver where it can be drained off.
Drain daily.
Install Drain
at Each Low Point
COMPRESSOR UNIT
Drain Daily
Drain Daily
Drain Daily
25 FEET OR MORE
Air Flow
(CFM)
10
20
30
40
50
70
50
1/2"
3/4"
3/4"
1"
1"
1"
100
3/4"
3/4"
3/4"
1"
1"
1"
150
3/4"
3/4"
1"
1"
1"
1-1/4"
200
3/4"
1"
1"
1"
1-1/4"
Length of Pipe (feet)