background image

Astria.US.com

126875-01_D

18

o  LIGHT Zone: LIGHT and light setting level is displayed
o  FAN Zone: FAN and fan setting level is displayed
o  TIME/PROG Zone: Current day indicator and current time is 

displayed

o  AUX Zone: Blank (AUX function is omitted on this control)
o  FLAME Zone: A&B Flame Icons and flame setting level numbers 

are displayed

Thermostat Disable Feature

•  The Thermostat Mode (described above) may be enabled if de

-

sired, but is disabled for applications where a thermostat is not 

allowed or undesirable.  THE FACTORY DEFAULT IS DISABLED.

•  When Thermostat Mode is Disabled:

o  The Modes of operation will cycle between MANUAL ON and 

MANUAL OFF (omitting THERMO).

o  Program Operation (described below) is also disabled.
o  The SET TEMP zone will be blank.
o  The room temperature will still be measured & displayed in the 

ROOM TEMP Zone.

o  The TIME/PROG zone will continue to display the Clock and Day 

of week, but none of the icons associated with Program Mode 

will be displayed.

•  To disable or re-enable the Thermostat, the transmitter must be 

in MANUAL OFF Mode, then press and hold the SET TEMP Zone 

and the DOWN Button simultaneously for 10-seconds. The LCD 

screen will go blank except either THERMO and OFF or THERMO 

and ON will flash 3-times (0.5-seconds OFF, 0.5-seconds ON) 

to indicate the change has been made.

• 
• 

FLAME - A (OR MAIN) ADJUSTMENT

• 

Transmits a flame height setting command to the control module 

to adjust the Flame-A height.

• 

Available settings are 1-7 with a factory default of 7. If the 

Flame-A setting is changed during operation (either manu-

ally or automatically), the control will remember and use the 

adjusted setting on subsequent manual ON cycles (Flame-A 

setting memory).

• 

While in MANUAL ON, or PROGRAM ON modes, press the 

FLAME Zone to enter Flame-A Adjustment, then press the UP or 

DOWN buttons to raise and lower the flame; press the MODE/

SET Button or wait for 15 seconds to accept the new setting.

• 

LCD Display: When setting the Flame-A height, the Flame-A 

icon, and Flame-A setting number will flash in the FLAME Zone.

LIGHT ADJUSTMENT

• 

Transmits a light setting command to the control module to 

adjust the light output level.

• 

Available settings are 0 (off) – 6 with a factory default of 0 (off).

• 

While in any mode of operation, press the LIGHT Zone to enter 

Light Adjustment, then press the UP or DOWN buttons to raise 

or lower the light output; press the MODE/SET Button or wait 

for 15 seconds to accept the new setting.

• 

LCD Displays:

• 

When raising or lowering the light output level with the UP 

or DOWN buttons, the light icon and light setting number 

will flash in the LIGHT Zone.

CONTINUOUS PILOT OPERATION

• 

To activate or deactivate the Continuous Pilot Feature, press 

and hold the MODE/SET and UP Buttons simultaneously for 5 

seconds.

• 

LCD Display: When activated, CONT. PILOT will be displayed in 

the MODE Zone.

CHILD-LOCK OPERATION

• 

Child-Lock operation prevents any user input to the transmitter. 

No mode of operation or feature may be adjusted when Child-

Lock is activated. All automatic functions will continue normally.

• 

To activate or deactivate the Child-Lock feature, press and 

hold the MODE/SET and DOWN Buttons simultaneously for 5 

seconds.

• 

LCD Displays:

• 

When activated, the LOCK icon will appear in the MODE 

Zone.

• 

If any touch-zone or button is pressed when activated, the 

LCD backlight will illuminate and the LOCK icon will flash 

for 5 seconds in the MODE Zone.

SENSOR SAFETY OVERRIDE

• 

Will only operate if the control is in MANUAL OFF mode.

• 

Press and hold the FLAME Zone and the UP Button simultane-

ously activate the sensor safety override feature.

• 

The module will ignore any sensor faults, continually emit an 

igniter spark, and energize the PILOT operator output.

• 

When the buttons are released, the control will immediately 

return to MANUAL OFF mode.

• 

LCD Display:

• 

When the Sensor Safety Override feature is activated, CONT. 

PILOT will flash on the LCD screen.

COMMUNICATION SAFETY

• 

In manual ON and program modes of operation, the transmitter 

will send a communication safety transmission every 15 - min-

utes. This signal is further processed by the ignition control 

module to verify the transmitter is communicating properly.

Summary of Contents for Paris Lights 43ZMN

Page 1: ...r adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 5 of this manual WARNING If the information in these instructions is not followed...

Page 2: ...ore trying to assemble operate or service this heater Improper use of this heater can cause serious injury or death from burns fire explo sion electricalshockandcarbonmonoxidepoisoning DANGER Carbon m...

Page 3: ...replace is designed to be smokeless If logs ever appear to smoke turn off fireplace and call a qualified service person Note During initial operation slight smoking could occur due to log curing and f...

Page 4: ...ASSACHUSETTS REQUIRE MENTS These appliances are approved for installation in the US state of Mas sachusetts if the following additional requirements are met Un vented Room Heaters shall be installed i...

Page 5: ...gs exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed and b weather stripping has be...

Page 6: ...ortoadjoining room or add ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors C Install a lower Btu Hr fire...

Page 7: ...moisture See Air for Combustion and Ventilation page 5 CHECK GAS TYPE Use the correct gas type natural or propane LP for your fire place If your gas supply is not correct do not install fireplace Cal...

Page 8: ...1 3 6 C 18 4 4 D 16 5 2 E 14 A B C D E 1 2 3 4 5 Wall Supplied firebox hood must be used at all times Note All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf No...

Page 9: ...75 01_D 9 17 1 2 29 7 8 29 7 8 16 3 8 7 1 8 1 7 8 8 1 4 44 1 8 1 1 55 1 8 52 47 16 1 2 11 3 4 8 1 4 5 8 INSTALLATION Continued Figure 8 ParisLights43 Series Dimensions Gas Line Access Gas Line Access...

Page 10: ...e LP supply This fireplace requires anexternalregulator notsupplied Installtheexternal regulatorbetweenthefireplaceandpropane LPsupply WARNING Never connect natural gas fireplace to private non utilit...

Page 11: ...trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap is not installed or is instal...

Page 12: ...o gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 13 2 Pressurize supply piping system by either openin...

Page 13: ...uide screw the rear panel to the fireplace as shown in Figure 16 INSTALLING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 17 2 Tighten screws securing ho...

Page 14: ...place unscrew 4 corner brackets from the firebox top See Figure 21 2 Remove 2 side walls and then the rear wall Discard rear wall 3 Replace 2 side walls and reinstall the corner brackets Installing Ac...

Page 15: ...urner shuts OFF Figure 26 Gas Module Right Side Figure 27 Gas Module Left Side Remote Control Feature The module has a built in remote control receiver that allows the user to program the remote trans...

Page 16: ...lied with the unit into the battery compart ment It is recommended that ALKALINE batteries always be used for this product Be sure the batteries are installed with the and ends facing the correct dire...

Page 17: ...default or degrees C Press the UP and DOWN Buttons simultaneously to change between degrees F and C SET TEMP While in THERMOSTAT mode press the UP or DOWN Button to change the SET TEMP 45 90 deg F 7 3...

Page 18: ...e A icon and Flame A setting number will flash in the FLAME Zone LIGHT ADJUSTMENT Transmits a light setting command to the control module to adjust the light output level Available settings are 0 off...

Page 19: ...liance requires 120V electricity for normal operation Control module should be plugged into electrical outlet located underneath firebox bottom Back up battery supply is available for power outages 1...

Page 20: ...end using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions...

Page 21: ...e running Some burner flame holes may become blocked by debris or rust with no flame present If so turn off fireplace and let cool Remove blockage Blocked burner flame holes will create soot BURNER FL...

Page 22: ...V MAX 15 AMPS 110V POWER IPI I S MAX 15 AMPS To Rocker Switch To J Box To J Box Pilot Main HI LO DC Motor Drive Light Module Black Black Brown Red Orange Orange To Ground Igniter Sensor PILOT BATTERY...

Page 23: ...t local propane LP gas company 3 Clean ODS pilot see Cleaning and Main tenance page 20 or replace ODS pilot assembly 4 Replace gas regulator 1 Contact local natural or propane LP gas company 2 Clean b...

Page 24: ...ng while cooling 1 Burner orifice is clogged or damaged 2 Damaged burner REMEDY 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance page 20 1 Refer to Air for Combus...

Page 25: ...y 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Control valve or gas control...

Page 26: ...Astria US com 126875 01_D 26 PARTS MODELS PARISLIGHTS43ZMN PARISLIGHTS43ZMP 11 7 4 3 8 8 8 8 14 15 16 17 18 19 20 24 21 5 22 23 6 2 1 13 10 9 12...

Page 27: ...Spark Wire 4 6 J7053 Orifice 32 1 J6989 Orifice 49 1 7 J6819 Brass Elbow 1 8 J6757 Light Bulb G9 120V 20W 4 9 J5207 Flat Washer 7 10 J4775 Bulkhead Fitting 1 11 J6834 Brass Elbow 2 12 J4714 Flextube...

Page 28: ...Astria US com 126875 01_D 28 PARTS MODELS PARISLIGHTS43ZMN PARISLIGHTS43ZMP 1 4 6 2 8 9 7 5 3 5 11 12 13 14 10 7 8...

Page 29: ...e of non approved parts can result in poor performance and safety hazards KEY NO CATALOG NO DESCRIPTION ParisLights43ZMN F1219 ParisLights43ZMP F1220 QTY 1 J6630 Top Spacer 4 2 J6566 Top Nailing Flang...

Page 30: ...ease contact your dealer IHP 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Visit us at Astria US com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed igni...

Page 31: ...riot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to n...

Page 32: ...name P126875 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Co...

Reviews: