5.4 Initial operation

After all connections have been made and checked, carry out the following procedure:

1.

Switch on the filtration pump. Check for leaks and verify that water is flowing to and from the swimming pool.

2.

Connect power to the heat pump and press the On/Off button

on the electronic control panel.

The unit will start up after the time delay expires (see below).

3.

After a few minutes, check whether the air blowing out of the unit iscooler.

4.

When the filtration pump is turned off, the unit should also turn off automatically.

5.

Allow the heat pump and the filtration pump to run 24 hours a day until the desired water temperature is

reached. The heat pump will stop running at this point +1°C. After this, it will restart automatically (as long as
the filtration pump is running) whenever the swimming pool water temperature drops 1 degree below the set
temperature (for example, if you set the temperature 28°C, the heat pump will stop when the temperature at
29°C. While it will restart when the temperature of the water down to 27°C)

Depending on the initial temperature of the water in the swimming pool and the air temperature, it may take
several days to heat the water to the desired temperature. A good swimming pool cover can dramatically
reduce the required length of time.

NOTE

Water Flow Switch:

It is equipped with a flow switch for protecting the HP unit running with adequate water flow rate. It will turn
on when the filtration pump runs and shut it off when the pump shuts off.

Time delay -

The heat pump has a built-in 3-minute start-up delay to protect the circuitry and avoid excessive

electrical contactor wear. The unit will restart automatically after this time delay expires. Even a brief power
interruption will trigger this time delay and prevent the unit from restarting immediately. Additional power
interruptions during this delay period do not affect the 3-minute duration of the delay.

5.

5.

5.

Location

Location

Location

and

and

and

connection

connection

connection

Summary of Contents for PRO ELYO INVERBOOST NN

Page 1: ...WEMBAD WARMTEPOMP Gebruiker en service manual BOMBA DE CALOR PARA PISCINA Manual del usuario y de servicio SCHWIMMBAD W RMEPUMPE Benutzer und Wartungshandbuch PISCINA POMPA DI CALORE Istruzioni per l...

Page 2: ...9 SWIMMING POOL HEAT PUMP PRO ELYO INVERBOOST NN User and Service manual...

Page 3: ...nection 6 Electrical Wiring 7 Start up of the Heat Pump 8 Troubleshooting 9 Exploded Diagram Thank you for using PRO ELYO INVERBOOST NN swimming pool heat pump for your pool heating it will heat your...

Page 4: ...Pump Water connection assembly 50 mm pcs 2 User and service manual Reducer connection 10 meters signal wire Waterproof box Winter cover Anti vibration base pcs 4 1 2 Dimension Model 71676 1 1 1 Descr...

Page 5: ...12 Models 71677 71678 71679 Models 71680 71681 1 1 1 Description Description Description...

Page 6: ...13 Models 71682 71683 68821 68822 68823 1 1 1 Description Description Description...

Page 7: ...st be stored and transferred in vertical position in its original packaging If it is not the case it cannot be operated until a minimum period of 24H has passed before the unit can have the electrical...

Page 8: ...78 Heating capacity Kw 2 41 1 5 3 13 2 0 3 87 2 7 5 1 3 15 Power consumption Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 General data Compressor type MITSUBISHI INV...

Page 9: ...apacity Kw 5 8 3 6 7 58 4 3 10 4 5 9 12 74 7 4 Power consumption Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 General data Compressor type MITSUBISHI INVERTER COMPRE...

Page 10: ...ty Kw 10 4 5 9 11 6 3 1 11 6 3 1 Power consumption Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 General data Compressor type MITSUBISHI INVERTOR COMPRESSOR Voltage V 380V 50Hz or 60H...

Page 11: ...y Pass Kit The By Pass Kit is the essential accessory for the installation of your heat pump it is also a tool for the optimization of the heating of the water The valves allows the optimum flow of wa...

Page 12: ...Water Inlet outlet connection 1 Install the two joints like the picture shows 2 Screw them onto the water Inlet outlet connection Mains Cable wiring 1 Open the cover of the terminal box marked red on...

Page 13: ...e air inlet Such locations impair the continuous supply of fresh air resulting in reduced efficiency and possibly preventing sufficient heat output 5 1 Heat pump location The unit will work properly i...

Page 14: ...he heat exchanger For this reason equipment of this sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent reverse f...

Page 15: ...heat pump will not start up if the water is not circulating 5 3 Typical arrangement This arrangement is only an illustrative example NOTE The factory supplies only the heat pump All other components i...

Page 16: ...et the temperature 28 C the heat pump will stop when the temperature at 29 C While it will restart when the temperature of the water down to 27 C Depending on the initial temperature of the water in t...

Page 17: ...water leak 5 6 Pressure gauge display R32 Examine the pressure gauge which indicates the refrigerant gas pressure of the unit the below table shows the normal value of the gas pressure R32 when the m...

Page 18: ...25 6 1 Inverter swimming pool heat pump wiring diagram Ref 71676 71677 71678 71679 71680 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 19: ...26 6 2 Inverter swimming pool heat pump wiring diagram Ref 71681 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 20: ...27 6 3 Inverter swimming pool heat pump wiring diagram Ref 71682 71683 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 21: ...28 6 4 Inverter swimming pool heat pump wiring diagram Ref 68822 R410A 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 22: ...ming pool heat pump wiring diagram Ref 68821 68823 R410A Above electrical wiring diagram only for your reference please subject machine posted the wiring diagram 6 6 6 Electrical Electrical Electrical...

Page 23: ...acceptable voltage variation is 10 during operation The connections must be dimensioned according to the power of the device and the state of installation Models Circuit breaker Maximum length of the...

Page 24: ...the control panel photo1 The other end of the signal wire photo2 Open the cover of the terminal box and pass through it the cable of the remote screen photo3 4 Insert the wiring into the designated p...

Page 25: ...32 Dry contact timer connection Timer Dry contact pump connection 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 26: ...ater temperature and the operation mode Press to stop the heat pump unit and show OFF Notice During the parameter checking and setting press the to quick exit and save the current setting Press again...

Page 27: ...equency limitation code 0 No frequency limit 1 Coil pipe temperature limit 2 Overheating or overcooling frequency limit 4 Drive Current frequency limit 8 Drive voltage frequency limit 16 Drive high te...

Page 28: ...D6 PAC PROELYO INVERBOOST NN 35 35 8Kw 68823 0CD7 PAC PROELYO INVERBOOST NN 35T 35 8Kw Product code parameter P Modbus Only Press for 5 second the first digital number flashes press or to choose the t...

Page 29: ...7 2 9 Press this button the light will be flash the heat pump will operate in Full output only 7 2 10 While you choose the Smart the heat pump will just operate in Medium output and Full output When i...

Page 30: ...he unit is on or off Operation logic of Auto Mode Set water temperature Tset Current water in temperature Tset 2 Current working mode After 3 minutes or above it will switch to Tset eg 28 Tset 2 eg 30...

Page 31: ...t 3 minutes after the filtration pump exit the standby mode to detect the water temp T1 again Cooling mode T1 Tset 1 last for 30 minutes T1 29 last for 30 minutes Filtration pump will enter standby mo...

Page 32: ...l be in Standby stop working until the water temperature drops to less 28 8 When you select the Powerful working mode T1 Tset 1 T1 29 Powerful mode frequency F10 F9 9 T1 Tset 1 T1 29 HP will be in Sta...

Page 33: ...quency F2 F1 7 T1 Tset T1 28 Smart mode frequency F5 8 When you select the Powerful working mode T1 Tset 1 T1 27 Powerful mode frequency F10 F9 9 T1 Tset 1 T1 27 Standby 10 Re start to cool water in s...

Page 34: ...nsor failure T6 PP06 1 The sensor in open or short circuit 2 The wiring of sensor is loose 1 Check or change the sensor 2 Re fix the wiring of the sensors Antifreeze protection in Winter PP07 Ambient...

Page 35: ...s been blocked 4 Exhaust temp Sensor failure 1 Check the high pressure gauge if too low fill with some gas 2 Check the waterway system and filtration pump 3 Check the piping system if there was any bl...

Page 36: ...he current becomes larger 4 Compressor or driver board damaged 1 Program error turn off electricity supply and restart after 3 minutes 2 Change driver board 3 Check compressor sequence connection VDC...

Page 37: ...DC motor is damaged 2 Main board is damaged 3 The fan blade is stuck 1 Detect DC motor replace with a new one 2 Change a new main board 3 Find out the barrier and work it out PFC module thermal circu...

Page 38: ...a new one Ambient Temperature device failure on Driver board EE24 Ambient Temperature device failure Change driver board or main board Compressor phase failure EE25 Compressors U V W are connected to...

Page 39: ...r 7 LED controller displays PP11 for water over cooling protection EE04 Water Overheating Protection PP11 Water Overcooling Protection For example as below Mode Output water temperature Set point temp...

Page 40: ...s show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode verifying the water inlet and...

Page 41: ...48 9 1 Exploded Diagram Mode 71676 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 42: ...3060123 Tube 16 1330900261 Left side panel 49 121000006 4 way valve 17 132000015 Fan blade 50 150000110 Drainage plug 18 1330900251 Front panel 51 117110012 Water inlet temp sensor T1 TH6 19 108010014...

Page 43: ...50 9 3 Model 71677 71678 71679 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 44: ...on piping 16 1330900261 Left side panel 50 113070044 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 1330900...

Page 45: ...16 1330900261 Left side panel 50 113070044 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 133090025 Front...

Page 46: ...16 1330900261 Left side panel 50 113070041 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 1330900251 Front...

Page 47: ...54 9 7 Model 71680 71681 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 48: ...changer 17 1332600051 Left side panel 53 119000021 EEV 18 1332600031 Front panel 54 113080056 EEV to distribution piping 19 108170017 Fan grill 55 150000110 Drainage plug 20 108560036 Base tray 56 108...

Page 49: ...exchanger 17 1332600051 Left side panel 53 119000021 EEV 18 1332600031 Front panel 54 113080056 EEV to distribution piping 19 108170017 Fan grill 55 150000110 Drainage plug 20 108560036 Base tray 56...

Page 50: ...57 9 10 Model 71682 71683 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 51: ...filter pipe 19 132000015 Fan blade 59 112100021 1 Water flow switch 20 108010024 Fan shaft cover 60 117110011 Water outlet temp sensor T2 TH5 21 133250004 Left side panel 61 108010025 Exchanger temper...

Page 52: ...filter pipe 19 132000015 Fan blade 59 112100021 1 Water flow switch 20 108010024 Fan shaft cover 60 117110011 Water outlet temp sensor T2 TH5 21 133250004 Left side panel 61 108010025 Exchanger temper...

Page 53: ...60 9 13 Model 68821 68822 68823 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 54: ...panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000001 2 Sealin...

Page 55: ...50001 Front panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000...

Page 56: ...nt panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000001 2 Sea...

Page 57: ...sure You should drain the water from the heat pump if it will stop running for a long time especially during the winter season or when the ambient temperature drops below 0 C 4 Check the water levels...

Reviews: