Parameter
Manual Description
App Description
Range
Default
Remark
19
Setting ofheat exchange ice
protection Tout
( too low water flow)
Protection water outlet
temp. cooling
3 ~ 20°C
5°C
Adjustable
20
Protection setting of
In-Out water temperature
Protection In-Out water
5 ~ 20°C
13°C
Adjustable
21
Protection water outlet temp.
heating
Protection water outlet
temp. heating
20~ 90°C
60°C
Adjustable
22
Time delay of compressor start
(after filter pump start)
Delay of compressor start
5 ~ 99S
60S
Adjustable
23
Time delay offilter pump stop
(after compressor stop)
Delay of filter pump stop
5 ~ 99S
30S
Adjustable
24
Setting Ambient temp. to Start
bottom heater
Bottom Heater Start
0 ~ 20°C
7°C
Adjustable
25
Setting Ambient temp. to change
fan speed
Setting Fan Speed Temp
5 ~ 40°C
27°C
Adjustable
26
Change Fahrenheit/C(0=C/1 =F)
Fahrenheit /C
0(C)/l(F)
0
Adjustable
27
Factory reset
Factory Reset
0(Reset)/
l(Existing
Setting)
1
Adjustable
Parameter table overview (2/2)
Remarks: To change the factory default via the phone, password is required and only available for
technician.
* Run 5m in /2 hr = fi lt er pump runs 5 min every 2 hours checking inlet temp., will run for 5 min, in this
period will disregard the flow switch.
** (O = m a nua l, in manual parameter 13 and 14 is enabled/ l=auto ma tic , in Automatic parameter 13
disabled only Parameter 12 & 14 is valid.)
Remarks: "┌" =" T", e.g. " ┌ 0" = T 0".
Parameter
Description
Range
Remark
T0
Water inlet temp.
-9 ~ 99°C
Measured Value
T1
Water outlet temp.
-9 ~ 99°C
Measured Value
T2
Evaporator coi! temp.
-9 ~ 99°C
Measured Value
T3
Ambient temp.
-9 ~ 99°C
Measured Value
T4
Compressor receiver temp.
-9 ~ 99°C
Measured Value
T5
Opening ofEEV
10 ~ 50 (1 =10P)
Measured Value
T6
Not used
-9 ~ 99°C
Measured Value
T7
Not used
-9 ~ 99°C
Measured Value
System measure value overview (2)