Communication extension card
-89-
Function
code
Name
Parameter description
Setting
range
Default
value
S7, S6, S5, HDIB, HDIA, S4, S3, S2,
and S1 in sequence)
10:
Virtual
output
terminal
command,
0x00–0x0F
(corresponding to RO2, RO1, HDO,
and Y1 in sequence)
11: Voltage setting (for V/F
separation)
(0–1000,
in
which
1000
corresponds to 100.0% of the rated
voltage of the motor)
12: AO output setting 1 (-1000–
+1000, in which 1000 corresponds
to 100.0%)
13: AO output setting 2 (-1000–
+1000, in which 1000 corresponds
to 100.0%)
14: MSB of position reference
(signed number)
15: LSB of position reference
(unsigned number)
16: MSB of position feedback
(signed number)
17: LSB of position feedback
(unsigned number)
18: Position feedback setting flag
(position feedback can be set only
after this flag is set to 1 and then to
0)
19–31: Reserved
P16.43
Transmitted
PZD2
0: Invalid
1: Running frequency (×100, Hz)
2: Set frequency (×100, Hz)
3: Bus voltage (×10, V)
4: Output voltage (×1, V)
5: Output current (×10, A)
6: Actual output torque (×10, %)
7: Actual output power (×10, %)
8: Rotating speed of the running
(×1, RPM)
9: Linear speed of the running (×1,
m/s)
10: Ramp frequency reference
11: Fault code
0–31
0
P16.44
Transmitted
PZD3
0–31
0
P16.45
Transmitted
PZD4
0–31
0
P16.46
Transmitted
PZD5
0–31
0
P16.47
Transmitted
PZD6
0–31
0
P16.48
Transmitted
PZD7
0–31
0
P16.49
Transmitted
PZD8
0–31
0
P16.50
Transmitted
0–31
0