21
INSTALLATION AND OPERATION MANUAL
• emerGency shut Down of the Boiler
If for some reason you must immediately shut down the operating boiler, by any means do not pour water on the kindling
wood! The boiler can burst!
It is very convenient to use dry sand for emergency extinction. There should be ~50kg of dry sand in the boiler room. Sand
not only isolates burning firewood well from the air oxygen but also cools down the burning zone. Then, when the boiler
cools down, sand can be easily cleaned and removed.
8. PossIble faUlTs
fault
cause
Problem solution
1. The set
temperature
cannot be reached
Not enough water in the heating system
Fill up
Too low temperature of the return water
Raise the return water temperature
Thermoregulator or ventilator is defective
Repair or replace
Poor quality fuel: high moisture content,
too large pieces of firewood
Use dry fuel, split firewood
Heating surfaces of the boiler are very dirty
Clean
No draught in the chimney due to accumulated impurities Clean
The ceramic burner is congested
Clean
Ventilator damper is stuck
Move or clean
2. smoke escapes
through the boiler
door
The door-sealing rope is damaged
Replace with a new one
Door is not tight along the entire perimeter
Adjust hinge supports and door lock (regulated
screwing or unscrewing of door hinge or lock screws)
(see Fig. 13)
13 pav. Durelių ir užrakto mechanizmo reguliavimas
Fig. 13 Adjustment of the door and lock mechanism
No draught in the chimney due to accumulated impurities Clean
3. Ventilator is not
operating
Emergency thermostat has tripped, light of the
ventilator switch is off
Unsrew the thermostat 1 (Fig. 10) cover and press
the button under it. It is absolutely required to
define and remove the causes of tripping of this
thermostat in order to avoid hazards to property and
human health!
Electronic regulator KR-4.3 or ventilator is faulty
Replace
Power supply failure
Check electric fuses of the electric panel of the
building; call electrician
Lamp 4 lights up (Fig. 11, see technical description of
regulator KR- 4.3)
All firewood has burned. Load more firewood, kindle
the boiler
9. WaRRanTY anD ITs ValIDITY TeRMs
The manufacturer provides a warranty for the boilers, the main conditions of which are the following:
• the connection of the boiler to the heating system as well as the initial kindling, adjustment and repairs are carried out by an
authorised company;