![ASTEL MGR100 Operating Instructions Manual Download Page 19](http://html.mh-extra.com/html/astel/mgr100/mgr100_operating-instructions-manual_2989704019.webp)
19
Alarm set-up
To set-up the alarming of the unit:
Write the GSM numbers for receiving SMS to the SIM card location from 43 to 52.
Write the phone numbers for calling to the SIM card location from 90 to 99.**
Write the location of the first GSM number for receiving SMS to the SIM card location 8.
Write the location of the last GSM number for receiving SMS to the SIM card location 9.
Write the location of the first phone number for calling to the SIM card location 1.**
Write the location of the last phone number for calling to the SIM card location 2.**
Set all the alarms status and triggering by instructions
ADS, ADT, AAS*, AAT*, ATS*, ATT*
and
on the models with GPS receiver also by the
AGS***, AGT***, AGC***
or
AGMx***.
When the remote control is used set the switching-on/off of alarming by instructions
REMKON*
or
REMDON
and audio or other indication by instructions
RELxREM*
or
OCExREM*.
When the relays are used with alarming set the relay time by instruction
RELxALM*.
Switch-on the alarming by instructions
ALMON
or
ALMONhh.mm.ss
or with remote control.
Other functions
To receive the status of digital inputs:
DIG
Received SMS:
NAME
D1:IN1:LOW
D2:IN2:LOW
D3:IN3:LOW
D4:IN4:HIGH
D5:IN5:HIGH
D6:IN6:HIGH
D7:IN7:LOW
D8:IN8:HIGH
To receive the voltage on the analog inputs:
ANG*
Received SMS:
NAME
A1:V1:11.0V
A2:V2:5.8V
A3:V3:5.9V
A4:V4:10.5V
A5:DC:9.5V
A6:ACCU:9.5V
To receive the temperature on the temperature sensors:
TMP*
Received SMS:
NAME
T1:TEMP1:23.5C
T2:TEMP2:23.0C
T3:TEMP3:22.0C