To define alarm triggering on digital inputs:
ADTxxxxxxxx
x=1 or 0
1-
to activate the alarm when the input is high – open contact
0-
to activate the alarm when the input is low – close contact
ADT11100000
(1.,2. – high inputs, 3, 4.,5.,6.,7.,8., - low inputs)
Alarming:
Received SMS:
NAME
ALARM:IN3:LOW
Analog inputs*
To receive alarm status on analog inputs:
AAS
Received SMS:
NAME
ALM:
A1:V1:OFF
A2:V2:OFF
A3:V3:OFF
A4:V4:ON
A5:DC:ON
A6:ACCU:ON
To enable alarms on analog inputs:
AASxxxxxx
x=1 or 0
AAS000111
(to enable alarm on analog input 4,5,6)
To receive alarm triggering on analog inputs:
AAT
Received SMS:
NAME
TRG:
A1:Low:10.2V
High:20.2V
A2:Low:0.0V
High:30.0V
A3:Low:0.0V
High:30.0V
A4:Low:11.0V
High:30.0V
A5:Low:10.0V
High:14.0V
A6:Low:10.0V
High:14.0V