V3.5 14/08/19
UD0089
Page 65
This Document is uncontrolled unless over stamped "CONTROLLED DOCUMENT"
2.3.9.2
CONNECTING THE MAINS POWER SUPPLY
GB - Traka Key Control and Intelligent Locker products are supplied without a plug and will need to be wired into a
non-switched fused spur.
FR - Les armoires de gestion de clefs et les casiers intelligents sont fournis sans prise électrique, ils devront être
raccordés à une boite de raccordement sans interrupteur et protégés par un fusible.
NOTE:
Before wiring the Traka power supply mains lead into the non-switched fused spur, please ensure
that the spur has been isolated at the main consumer unit or fuse box. If you have any doubt about
connecting Traka to the mains power obtain expert advice before continuing.
The mains cord from the power supply will need to be fed through one of the knock out holes at the top or bottom of
the control pod. It is important to use the rubber grommet provided to protect the cable from being cut by the metal
work. The mains cable should also be run inside 20mm trunking to the non-switched fused mains spur.
NOTE:
THIS APPLIANCE MUST BE EARTHED!
NOTE:
The wires in this mains lead are coloured in accordance with the following code:
Green / Yellow: Earth
Blue: Neutral
Brown: Live
If the coloured wires of the mains lead of this appliance do not correspond with the coloured markings identifying the
terminals in your spur, proceed as follows:
The wire which is coloured GREEN AND YELLOW must be connected to the terminal in the spur which is
marked by the letter E or by the Earth symbol or coloured GREEN or GREEN AND YELLOW.
The wire which is coloured BLUE must be connected to the terminal in the spur marked with the letter N or
coloured BLACK.
The wire which is coloured BROWN must be connected to the terminal in the spur which is marked with the
letter L or is coloured RED.
NOTE:
A readily accessible mains disconnection device must be incorporated in the building installation
wiring and this device must enable double pole disconnection and have a minimum of a 3mm contact gap.
If you are installing the system outside of the United Kingdom or have any doubts about the installation,
please contact Traka or a Qualified Electrician for mains wiring assistance.