500-33520, Revision B  

Page 3 of 4 

Maintenance

 

The power supply and stand by battery(s) should be tested at least once a year as follows: 

1.  CHECK 

LED’s for normal state

:  AC ON Green, Trouble Normal ON Green, DC ON Red. 

2.  CHECK output voltage with normal load (assures proper voltage to float charge batteries):  For 12V setting, voltage should 

read between 13.6 VDC and 13.8 VDC; and for 24V setting, voltage should read between 27.1 VDC and 27.6 VDC. 

3.  DISCONNECT AC input:  AC LED should be off, and 

all other LED’s should remain normal.

 

4.  CHECK DC output to be above 12.0 VDC for 12V setting and 24.0 VDC for 24V setting (checks standby batteries to be 

operational). 

5.  APPLY AC and VERIFY AC LED ON. 

 

Battery Selection 

The table below shows typical standby time in hours for various loads and batteries.  The table works for either 12 VDC or 24 VDC.  
The AQD6 was evaluated at UL with a 75 Ah sealed lead acid battery. 

 

 

Approximate Battery Standby Time Table with a reserve of 6A for 5 minutes for Alarm  

Total Output 

in 

Amps 

4 AH 

Battery 

Standby 

7 AH 

Battery 

Standby 

12 AH 

Battery 

Standby 

24 AH 

Battery 

Standby 

40 AH 

Battery 

Standby 

75 AH 

Battery 

Standby 

0.06 

53 

101 

180 

371 

625 

1180 

0.125 

25 

48 

86 

178 

300 

566 

0.25 

13 

24 

43 

89 

150 

283 

0.50 

6.4 

12.1 

21.6 

44.5 

74.9 

142 

3.2 

6.0 

10.8 

22.2 

37.5 

71 

1.6 

3.0 

5.4 

11.1 

18.7 

35 

1.1 

2.0 

3.6 

7.4 

12.5 

24 

0.8 

1.5 

2.7 

5.6 

9.4 

18 

0.6 

1.2 

2.2 

4.4 

7.5 

14 

0.5 

1.0 

1.8 

3.7 

6.2 

12 

 

Summary of Contents for Securitron AQD6 Series

Page 1: ...wo PDB 8F AQD6 with two PDB 8C AQD6 with one PDB 8F8R AQD6 with one PDB 8C1R Description The AQD6 series are heavy duty self contained efficient clean offline switching power supplies with linear type performance and are jumper selectable between 12 VDC at 6A and 24 VDC at 6A The AQD6 series have a dedicated lead acid battery s charger that obtains maximum battery life while providing 12 VDC or 24...

Page 2: ... 50oC Product was not evaluated at UL for outdoor use DC LED Indicator Adjacent to DC terminal block Green Battery Charging 2P Terminal block marked Bat CAUTION To avoid spark AC must be applied before connecting battery cable to battery Fault reporting relay rating 32 VDC 120 VAC 1A The battery charger is precision set to float charge 12V or 24V sealed or wet lead acid batteries A 12 inch battery...

Page 3: ...etting checks standby batteries to be operational 5 APPLY AC and VERIFY AC LED ON Battery Selection The table below shows typical standby time in hours for various loads and batteries The table works for either 12 VDC or 24 VDC The AQD6 was evaluated at UL with a 75 Ah sealed lead acid battery Approximate Battery Standby Time Table with a reserve of 6A for 5 minutes for Alarm Total Output in Amps ...

Page 4: ...ing but not limited to installation error vandalism or act of God Replacement product is shipped at Securitron s expense next day air if needed For more information visit www securitron com Securitron is a brand associated with Hanchett Entry Systems Inc an ASSA ABLOY Group company Copyright 2016 Hanchett Entry Systems Inc All rights reserved Reproduction in whole or in part without the express wr...

Reviews: