background image

 

 

500-33520, Revision B 

Page 2 of 4 

CAUTION 
Damage  can  occur  when  switched  with  DC  output  load.  
Proper  voltage  must  be  confirmed  before  connecting 
devices. 
 
The AQD6 series are UL Listed and have additional supervisory 
features: 

 

Battery disconnect relay when battery(s) are depleted 

 

Set  of  F

orm  “C”  relay  contacts  that  indicate

  AC  power 

failure 

 

Set of F

orm “C” relay contacts 

that indicate low battery(s) 

 

DC Output is Class II power limited.   

 
Depending on load, low battery trouble indicates 50

75% battery 

capacity remaining.   Input wiring to the unit should be enclosed 
in conduit secured firmly to the enclosure. The AQD6 cannot be 
used to power a mercantile bell. 

 

 

Specifications 

AC Input:  L, N, G - 3P Terminal block 
Safety block with recessed hardware insulation accepts up to 
12 AWG  
L= Line, N= Neutral, and G = Ground 
AC Input  ......................................................... 120

240 VAC / 240W 

AC Input Frequency……………………

 ............................ 50 to 60 Hz 

 
AC LED Indicator (Panel mounted on the enclosure door) 
The AC indicator is a green LED.  This LED off with AC at the terminals 
would  indicate  a  blown  fuse  link.    A  blown  AC  fuse  link  would  indicate 
catastrophic failure and must be returned to the factory for repair. 
 
AC Input Voltage Selection 
 
CAUTION
 
To prevent damage, the power supply board must be configured for 
the proper voltage before applying line voltage. 
 
NOTE: 

Once the link is cut, there is no conversion back to 120 VAC. 

There  is  a  removable  link  located  at  the  top  right  of  the  power  supply 
board.  This link is cut and removed to convert to 240 VAC. 
 
DC Output Voltage Selector Jumper 
 
CAUTION 
To prevent damage, the DC load and battery(s) connections are 
removed before switching selector switch up or down. 
 
The jumper is slightly left of center near the AC terminal block, and is 
m

arked with “VOLTAGE SELECT 12V 

/ 2

4V”.  T

he jumper is moved to 

the appropriate pins to configure the output voltage. 
 
DC Outputs:  2P Terminal block 
NOTE:
  There is up to a 10-second delay for initial turn on. 
Output voltage Nominal  ............................................ 12 VDC / 24 VDC 
Output voltage Typical  ........................................   AC on 12.5V / 25.0V 
Output range with rated load  ............. 12.0

13.0 VDC / 24.5

25.5 VDC 

Output range on battery power ........... 9.79

13.2 VDC / 19.6

26.4 VDC 

Output continuous current (UL rating) ............................................... 6A 
Load regulation no load to max (no battery)  ............................... ±0.2% 
Output ripple full load ........................................................... 240 mV pp 
Current Overload Short Circuit Protection  ...................................... Yes 
Thermal runaway Protection  ........................................................... Yes 
Power Limited Output with Thermal Protection for Models AQD6-8F, 
AQD6-8C, AQD6-16F, AQD6-16C, AQD6-8F8R, and AQD6-8C1R. 
Non power limited for Model AQD6 
Current Overload and Thermal shutdown will auto-restart without 
removing load. 
Ambient operating temperature range  ......................... -20oC to +50oC 
Product was not evaluated at UL for outdoor use. 
DC LED Indicator (Adjacent to DC terminal block)  ..................... Green 
Battery Charging: (2P Terminal block marked [

Bat+]) 

 
CAUTION 
To avoid spark, AC must be applied before connecting battery cable 
to battery. 
 
Fault reporting relay rating:  32 VDC, 120 VAC, 1A 

The battery charger is precision set to float charge 12V or 24V sealed or 
wet lead acid batteries.  A 12-inch battery cable assembly is provided 
that plugs from module to battery:  Red (+), Black (

) Neg. 

Battery(s), any type of lead acid  ...................... 12V / 24V, 4 AH

40 AH 

 

UL evaluated  ..................................................................... 72AH 

Battery(s) recharge   ......................................................... 700 mA max 
Battery(s) average recharging current   ..................................... 250 mA 
Battery(s) PTC self-resetting circuit breaker  ............................. 6A PTC 
Battery(s) Reverse hookup protection  ..............................Yes, 4A PTC 
To estimate the recharge time in hours for depleted battery(s), the AH 
rating is multiplied by 4 (AH x 4).  As an example, a 12V system with two 
depleted 12V, 7 AH batteries would take about 28 hours to re-charge. 
AQD6 Supervised Added Features: 
UL Listed 
Class II Power Limited   ............................. Refer to DC outputs section 
AC Status Output Relay:  3P Terminal block  

AC Fail “C” contacts r

ating  ................................ 32 VDC, 120 VAC, 1A 

Three position AC fail terminal block marked “NO, C, NC” are shown in 

the Normal, energized, AC ON condition. 
Battery LED Indicator  ..................................................................... Red 
Battery Charge 
Battery Max. Charge (no load)   ......................................... 13.7V /27.4V 
Battery Cutoff internal relay contacts   ................. 32 VDC, 120 VAC,1A 

Low Battery Cutoff……………

.

……..

 ..... 9V /18 V for 12 V / 24V setting 

Battery Cutoff Relay is normally energized for fail-safe operation. 
Sealed lead acid batteries have a typical life of 3 to 5 years. 
Physical  
AQD6 Module Dimensions  ......................... 7.36

 L x 4.04

 W x 1.75

 H 

Height includes 7/16

” standoffs, not provided with module only.

 

Mounting Holes Center to Center  ............................. 6.44

 

W x 3.41”

 H 

AQD6 module only weight  ........................................................ 12.4 oz 
AQD6 in enclosure  ......................................................

14” x 

14

” x 3.

50

 

AQD6 in enclosure weight  ........................................................ 6.85 lbs 
UL Approvals for AQD6 
UL 294, 6

th

 Edition 

 Access Control System Unit 

 

Endurance Test Level 1 

 

Attack Test Level 1 

 

Battery Standby Test Level 4 

UL 603 

 Power supplies for Use with Burglar-Alarm Systems 

UL 1481 

 Power Supplies for Fire-Protective Signaling Systems 

ULC S318-96 

 Power supplies for Burglar Alarm Systems 

ULC  S533-02 

  Standard  for  Egress  Door  Securing  and  Releasing 

Devices 
 
For ULC-S318-96 compliance, the power supply battery fail line must be 
connected to and monitored by a control panel trouble zone. 
 
NOTE 1:
 

The AQD6 uses a standard power supply enclosure, not an 

attack proof’ enclosure.  As such, the AQD6 shou

ld not  be 

used to power a mercantile bell. 

NOTE 2: 

When  using  a  battery  that  is  not  housed  inside  the  power 
supply  enclosure,  the  battery  leads  require  protection  from 
the enclosure via the use of conduit. 

NOTE 3: 

When  using  the  AQD6B  in  another  enclosure,  minimum 
standard  spacing  between  live  electrical  circuits  shall  be 
taken into account.

 

Summary of Contents for Securitron AQD6 Series

Page 1: ...wo PDB 8F AQD6 with two PDB 8C AQD6 with one PDB 8F8R AQD6 with one PDB 8C1R Description The AQD6 series are heavy duty self contained efficient clean offline switching power supplies with linear type performance and are jumper selectable between 12 VDC at 6A and 24 VDC at 6A The AQD6 series have a dedicated lead acid battery s charger that obtains maximum battery life while providing 12 VDC or 24...

Page 2: ... 50oC Product was not evaluated at UL for outdoor use DC LED Indicator Adjacent to DC terminal block Green Battery Charging 2P Terminal block marked Bat CAUTION To avoid spark AC must be applied before connecting battery cable to battery Fault reporting relay rating 32 VDC 120 VAC 1A The battery charger is precision set to float charge 12V or 24V sealed or wet lead acid batteries A 12 inch battery...

Page 3: ...etting checks standby batteries to be operational 5 APPLY AC and VERIFY AC LED ON Battery Selection The table below shows typical standby time in hours for various loads and batteries The table works for either 12 VDC or 24 VDC The AQD6 was evaluated at UL with a 75 Ah sealed lead acid battery Approximate Battery Standby Time Table with a reserve of 6A for 5 minutes for Alarm Total Output in Amps ...

Page 4: ...ing but not limited to installation error vandalism or act of God Replacement product is shipped at Securitron s expense next day air if needed For more information visit www securitron com Securitron is a brand associated with Hanchett Entry Systems Inc an ASSA ABLOY Group company Copyright 2016 Hanchett Entry Systems Inc All rights reserved Reproduction in whole or in part without the express wr...

Reviews: