background image

Rixson® and Smok-Chek® are registered trademarks of Yale Security Inc., an ASSA ABLOY Group company.

Copyright© 2003, 2009, Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.

Reproduction in whole or in part without the express written permission of Yale Security Inc., is prohibited.

4. Making Adjustments to the Holder

A. Closer spring force should be as low as possible.

(Closer should arrive at lowest setting).

B. Turn 

OFF

Power (using ON/OFF switch).

C. To set Hold Open:

1.

Door should be in 

CLOSED

position.

2.

Raise or lower cam until the word “Push” is dis-
played from the 

UNDERSIDE

of the unit (Fig 4a).

3.

Open door to desired Hold Open position.

4.

Raise or lower cam and 

ROTATE

until pocket of 

cam is in position next to Roller A shown in Fig 4b

5.

Release cam to re-engage teeth.

6.

Turn 

ON

power (using ON/OFF switch).

7.

OPEN DOOR.

Door should stay in Hold Open 

position–if not, repeat Steps 3 and 4.

8.

Pull door 

OUT

of Hold Open–door should close 

freely.

9.

OPEN DOOR

. If releasing force needs to be 

increased, turn adjusting nut 

IN.

If lesser holding 

force is desired, turn nut 

OUT

.

10.

Attach holder cover.

Trouble-Shooting Tips:

1.

Turn ON power.

2.

Can door swing far enough to engage hold open? Minimum opening is 85°.

3.

Make sure closer is at lowest spring setting.

4.

Put piece of metal against the magnet to make sure it is receiving current.

5.

If not, double check wiring instructions.

6.

If so, with door in closed position look up at holder mechanism. Word PUSH should be visible, if 
not, adjust cam.

7.

Turn adjusting nut.

8.

Check arm indexing.

Page 4

ISFM0101

Fig 4a

Fig 4b

Hold Open
Adjust Nut

www.rixson.com

Push Side Mounting

ASSA ABLOY

RIXSON

®