Troubleshooting Recommendations - con’t

No 

Symptom 

Recommended Remedy 

The ADAEZ operator 
does not activate when 
pushing the INSIDE 
pushbutton 

·

 

If RF buttons are used and LED D3 is NOT flashing 
perform troubleshooting steps in section “RF transmitters 
will not Sync to WIM” 

·

 

If hardwired buttons are used and D3 is NOT flashing: 

o

 

verify wires are connected to the Common (C) 
and Normall Open (NO) switch contacts. 

o

 

Use a multimeter to verify a contact closure on 
INSIDE BUTTON. 

·

 

IF LED D3 IS flashing &  LED D5 IS flashing 

o

 

Verify LEDs on setup board are lighting.  If LEDs 
on setup board do not light, Erase all learned 
codes from the ADAEZ operator and re-sync the 
WIM to the operator. 

o

 

Verify ADAEZ operator has been programmed using 
the procedure in the Installation and Operating 
Instructions. 

·

 

IF LED D3 IS flashing and LED D5 is NOT flashing 

o

 

Verify the jumper on the FIRE PANEL is in place. 

·

 

Turn the Signal Delay switch to the “ON” position. 

The ADAEZ operator 
does not activate when 
pushing the OUTSIDE 
pushbutton 

·

 

If RF buttons are used and LED D4 is NOT flashing 
perform troubleshooting steps in section “RF transmitters 
will not Sync to WIM” 

·

 

If hardwired buttons are used and D4 is NOT flashing: 

o

 

verify wires are connected to the Common (C) 
and Normall Open (NO) switch contacts. 

o

 

Use a multimeter to verify a contact closure on 
INSIDE BUTTON. 

·

 

IF LED D4 IS flashing &  LED D5 IS flashing 

o

 

Verify LEDs on setup board are lighting.  If LEDs 
on setup board do not light, Erase all learned 
codes from the ADAEZ operator and re-sync the 
WIM to the operator. 

o

 

Verify ADAEZ operator has been programmed 
using the procedure in the Installation and 
Operating Instructions. 

·

 

IF LED D3 IS flashing and LED D5 is NOT flashing 

o

 

Verify the ACCESS CTR IN contact is closed 
while activation is being sent.  The WIM will not 
accept an OUTSIDE activation unless a valid 
access control input is received. 

o

 

Verify OUTSIDE BUTTON DISABLE contact is not 
closed. 

o

 

Verify the jumper on the FIRE PANEL is in place. 

o

 

Turn the Signal Delay switch to the “ON” position. 

 

Summary of Contents for Norton ADAEZ

Page 1: ...approved by the party responsible for compliance could void the user s authority to operate this device INSIDE BUTTON INSIDE BUTTON PRESS RELEASE TO LEARN HOLDTO ERASE OUTSIDE BUTTON DOOR OPERATOR FIR...

Page 2: ...ual provides system description installation instructions operating instructions and troubleshooting recommendations for the ADAEZ Wireless Interface Module referred to as the WIM The ADAEZ WIM allows...

Page 3: ...ADA1015C is provided to plug in the ADA EZ swing door operator into the WIM module 3 Access Control Contacts are provided to interface the WIM with access control 4 Lock Interface Contacts are provide...

Page 4: ...If a DC power supply is used connect the ground to the terminal marked and the positive to the terminal marked c If the operator will be powered through the WIM power is properly applied to the ADAEZ...

Page 5: ...ng door operator for proper operation 7 Erase All RF Codes from the Door Operator Figure 2 Figure 3 3 On the Setup board LEDs DS8 through DS11 shall rapidly flash GREEN 3 times 1 Refer to Figure 3 and...

Page 6: ...tivation signal to the door operator ONLY if the ACCESS CTR INPUT contact is CLOSED d The LED will flash and the audible will beep 4 times if the RF signal was successfully learned e If the pushbutton...

Page 7: ...IM INSIDE BUTTON INSIDE BUTTON PRESS RELEASE TO LEARN HOLDTO ERASE OUTSIDE BUTTON DOOR OPERATOR FIRE PANEL IN COM OUT ACCESS CTR OUTSIDE BUTTON DISABLE LOCK POWER NO COM NC LOCK OUTSIDE BUTTON PRESS R...

Page 8: ...between receiving an activate signal and sending an activate signal to the door operator This allows additional time for the lock to unlock before the door starts to unlock before the door starts to...

Page 9: ...nnect the optional Access Control Input contact Alarm Panel Output contact or Fire Panel Input contact Closing the ACCESS CTRL IN contact will switch the state of the LOCK contact and enable the OUTSI...

Page 10: ...ushbutton signal is received 1 Refer to Figure 6 and Connect the OUTSIDE PUSHBUTTON DISABLE contact to the deadbolt monitoring switch Placing a jumper across the ACCESS CTRL IN and COM will maintain t...

Page 11: ...CESS CTR OUTSIDE BUTTON DISABLE LOCK POWER NO COM NC LOCK OUTSIDE BUTTON PRESS RELEASE TO LEARN HOLDTO ERASE OPERATOR SIGNAL SIGNAL DELAY POWER IN 12 OR 24V CH S LOCK POWER SUPPLY FAIL SECURE FAIL SAF...

Page 12: ...N COM OUT ACCESS CTR OUTSIDE BUTTON DISABLE LOCK POWER NO COM NC LOCK OUTSIDE BUTTON PRESS RELEASE TO LEARN HOLDTO ERASE OPERATOR SIGNAL SIGNAL DELAY POWER IN 12 OR 24V CH S LOCK POWER SUPPLY FAIL SEC...

Page 13: ...white stripe is plugged into the terminal and the black wire is plugged into the terminal on both ends of the cable Verify the wires are fully seated into both green connectors on both ends of the cab...

Page 14: ...ck 6 Lock does not unlock when an OUTSIDE activation is sent If RF buttons are used and LED D4 is NOT flashing perform troubleshooting steps in section RF transmitters will not Sync to WIM If hardwire...

Page 15: ...FIRE PANEL is in place Turn the Signal Delay switch to the ON position 9 The ADAEZ operator does not activate when pushing the OUTSIDE pushbutton If RF buttons are used and LED D4 is NOT flashing per...

Page 16: ...armful interference 1 l appareil ne doit pas produire de brouillage Le pr sent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est au...

Reviews: