700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
13 of 17
17
Troubleshooting Recommendations
No
Symptom
Recommended Remedy
1
LED D8 does not light
Green when Operator
cable is plugged into WIM
and ADAEZ
·
If using the ADA1015P hardwire kit verify the black wire with
white stripe is plugged into the “-“ terminal and the black wire is
plugged into the “+” terminal.
·
If using Power supply by other, verify the wires from the power
supply are the correct polarity and plugged intot the “-“ and “+”
terminals.
·
Verify the wires are fully seated and making a good connection.
·
Using a multimeter, insert the probes into the holes below the “-
“ and “+” terminals and verify 12 or 24 Volts AC or DC voltage.
2
The LED on the ADAEZ
battery pack does not
light steady GREEN
when powered by the
provided operator cable
ADA1015C.
·
Verify that 24VDC is being supplied to the POWER IN
connection on the WIM and LED D8 near the connector is
lighted steady GREEN.
·
On the Operator Cable ADA1015C, Verify the black wire with
white stripe is plugged into the “-“ terminal and the black wire is
plugged into the “+” terminal on both ends of the cable.
·
Verify the wires are fully seated into both green connectors on
both ends of the cable.
·
Using a multimeter, insert the probes into the holes below the “-
“ and “+” terminals and verify 24 VDC on the Operator end of
the Operator Cable ADA1015C.
3
RF Pushbuttons or
Optional Handheld
Remote ADA1031 (Not
Included) will not Sync to
WIM
·
Verify the voltage of the CR2032 battery is above 3.0V and
replace battery if necessary.
·
Unwrap the antenna wire on the WIM and extend the wire
through a hole in the enclosure.
·
If programming an INSIDE BUTTON Press and hold the
INSIDE BUTTON switch on the WIM for 5 seconds to erase all
existing learned transmitters. Re-learn using procedure above.
·
If programming an OUTSIDE BUTTON Press and hold the
OUTSIDE BUTTON switch on the WIM for 5 seconds to erase
all existing learned transmitters. Re-learn using procedure
above.
4
Operator will not sync to
WIM
·
Verify the jumper on the FIRE PANEL contact is in place.
·
Verify the OUTSIDE BUTTON DISABLE contact is not closed.
·
Erase all existing RF codes from Operator (on the Operator
setup board, PRESS and HOLD LEARN, PRESS and
RELEASE RESET).