30
Basic Rain Sensor Function
Once the Rain Sensor detects rain, it will immediately activate
the windows to start closing to the chosen configuration,
i.e. shut or vent, and displays the icon shown here.
The windows will reopen 15 minutes after the Rain Sensor has dried.
Note: The sensor can be placed in open areas if desired and does
not need to be next to the assigned zone/window.
The Rain Sensor will not be activated by dew.
17
WIRING DIAGRAM
2 1
24 VDC 1AMP
+VDC -VDC
2 1
24 VDC 1AMP
+VDC -VDC
24 VDC 1AMP
NSW2 NSW1
+VDC -VDC
2 1
24 VDC 1AMP
2 1
Note:
A 120 Ohm terminal resistor must be placed at each end of the network.
1m min
from last junction.
+VDC -VDC
Max current
750mA
RAIN SENSOR:
Maximum of 4 per network. They can be assigned to specific zones. Option of close to shut or vent position. Option to re-open once the rain has stopped and the sensing circuit has dried. Rain Sensors can be overridden when wet, it will reset once dried. Max current 250mA.
NETW
ORK AD
APT
OR:
Can be placed anywhere on the network when used with a Rain Sensor
.
Max current 100mA.
30m Max
Note:
Dip switches do not require adjusting for use with a Rain Sensor
. They must
all be in the left hand position as shown.
KEYPAD:
Maximum of 2 per Network. They can be placed anywhere on the network. Max current 100mA.
+VE 24VDC - BRO
WN
+VE 24VDC - BRO
WN/WHITE
NOT USED - GREEN
-VE 24VDC - BL
UE/WHITE
-VE 24VDC - BL
UE
NOT USED - GREEN/WHITE
NSW2 - ORANGE
NSW1 - WHITE/ORANGE
SYNCHRONISA
TION CABLE CONNECT
IONS:
Each Actuator can have a synchronisation unit attached. The synchronisation unit is not connected to the network and therefore will not take up a position on the network.
Network dropper line 2m max.
CA
T 5e CABLE:
(T568B Wiring) 1m max long.
NSW2 - BROWN
NSW1 - WHITE
-VDC - BLACK
+VDC - RED
24 VDC 1AMP
WHITE GREEN BRO
WN
BL
UE
RED BLA
CK
1 2
24 VDC 1AMP
NSW1 NSW2 +VDC -VDC
+VDC -VDC
1 2
1 2
24 VDC 1AMP
+VDC -VDC
1 2
24 VDC 1AMP
Control Loom network dropper line. 2m max.
+VDC -VDC
24 VDC 1AMP
1m min
from last junction.
+VDC -VDC
Summary of Contents for Interlock Elevation Window Control System