Operate the Zone on the Home page displaying an explanation mark.
The window that does not move corresponds to the Actuator that has not
been recognized. Check for loose wiring to that Actuator.
If no loose wires are found then the Actuator could be at fault.
To remove this Actuator from the Zone so the warning is no longer displayed,
carry out the following steps:
Note: If a Rain Sensor is assigned to this Zone it will need to be removed before the
Actuator can be removed.
1. Press Setup,
Zone Setup
.
2. Press
Remove From Zone
.
3. Press the right hand side
arrow
keys to scroll to the Zone that is displaying an
explanation mark on the Home page.
4. If necessary, press the left hand side
arrow
keys and scroll to the Actuator
that is
coloured red
.
5. Press
Remove From Zone
.
6. Press
Setup
to go back to the Zone Setup page then press
Setup
again to go
back to the Setup page.
7. Press
Yes
to save your settings.
The warning should now be resolved in the Home page.
If not, contact your installer.
TROUBLE SHOOTING
18
RESTARTING THE KEYPAD
This function is used when a Zone warning is displayed on the Keypad indicating
that one or more of the Actuators have not been recognized by the Keypad.
1. Wait for at least 2 minutes.
If the warning is still present push Restart Keypad in the Setup page.
The Keypad should now recognize the Actuator.
If it does not, then follow the steps in the next section.
There are two ways to assign Actuators to zones:
1.
If serial numbers are known
(from page 26):
I
f not proceed to section 2 below.
Use the
arrow
keys to scroll, matching the serial number
on the left with the desired Zone on the right.
Press
Add to Zone
and confirm your selection.
2.
If serial numbers are not known:
Press each
Actuator
button on the left.
The corresponding Actuator will open.
Note: After 5 minutes it will close automatically.
Visually locate this Actuator. Then use the
arrow
keys on the right
to select the desired Zone.
Press
Add to Zone
and confirm your selection.
The window will now close if open.
Note: Pressing the Actuator button again will also close the window.
Repeat either process until all Actuators are allocated to your
desired Zones.
Press
Exit & Save
then
Yes
to save your Zone settings.
5