In the deliver state, the value for the time is preconfigured with 12 months. Maintenance can be
parameterized as follows:
-
Menu: „Service Menu“, „Password Input“: Enter password
-
Menu: „Settings“, „SpecParameter“, „Serv.Interv. mth“: Set to „mm“
The entry „mm“ defines the number of months until the maintenance requirement. The value 0
means: no time-based maintenance requirement. The maximum configurable value is 60, which
corresponds to 5 years. Since there is no integrated real-time clock module, the time is only
counted when the control system is turned on.
6.3.16 Parameterize maintenance requirement for relay output
A maintenance requirement for the control system can also be parameterized for a relay output via
a menu entry. The corresponding relay is switched to active as soon as one condition for the
maintenance requirement is fulfilled. It can be used for signaling purposes.
6.3.17 Parameterize maintenance requirement for blinking light
A maintenance requirement can also be triggered for an additional blinking light action via a menu
entry. As soon as one condition for the maintenance requirement is fulfilled, the blinking light is
kept active for a few seconds longer after each run to the gate‘s end position (blinking light only
goes out 4, 8 or 12 seconds after motor shutdown).
The blinking lights are additionally activated for the maintenance requirement as follows:
-
Menu: „Service Menu“, „Password Input“: Enter password
-
Menu: „Settings“, „SpecParameter“, „Service Action“: Set 0 to 7
The following actions are linked to the configured parameter value:
Parameter
value
Blinking light function in terms of maintenance requirement
0
No additional blinking light function
1
The blinking light remains switched on for four seconds longer after the OPEN or
CLOSE gate position is reached
2
Blinking light remains switched on for 8 seconds longer
3
Blinking light remains switched on for 12 seconds longer
6.3.18 Resetting the maintenance requirement
The text „< MAINTENANCE > required“ will always periodically appear on the LC display as long
as the maintenance requirement has not been dealt with or confirmed by the service technician in
the control system‘s menu. In addition, the blinking light is kept active for a few seconds longer
after every movement to the gate‘s final position (when this has been parameterized).
Furthermore, a relay output can be parameterized and then switched to active.
After successful maintenance of the gate and testing of the safety functions by qualified personnel,
this can be confirmed in the control system in the following manner and thus the maintenance
requirement can be reset:
-
Menu: „Service Menu“, „Password Input“: Enter password
-
Menu: „Diagnosis“, „Gate State“, „RESET Service“