In the default setting for variant 1, the PartialOPEN command function is on the input terminal In4.
Input In3 is assigned the function toggle switching impulse.
The following alternative input functions can be selected for both of the yellow marked inputs „In4“
and „In3“ under the submenu „Settings“:
Variant 2
Terminal No.
Designation
Input function
7
In4
PartialOPEN impulse (pedestrian passage)
8
In3
CLOSE impulse
Variant 3
Terminal No.
Designation
Input function
7
In4
CLOSE impulse
8
In3
TOGGLE switching impulse
(OPEN /STOP/CLOSE /STOP / ...)
6.3.6 CLOSE operating element
A button that generates a movement command in the gate CLOSE direction can be connected to
input „In3“ (variant 2) or „In4“ (Variant 3). The function is only supported in automatic operation.
- Switch control system to a zero-potential state
- Connect CLOSE button to input terminal In3 or In4 and +24V (make contact)
- Switch on power supply for control system
-
Check button‘s function
6.3.7 Set up partial OPEN function (pedestrian passage)
A button or switch contact (closer) is connected to input In4 (variants 1 and 2) to set up a Partial
OPEN function (pedestrian passage). The function is only supported in automatic operation.
-
Switch control system to a zero-potential state
-
Connected button/switch for Partial OPEN to input In4 and +24 V
-
Switch on power supply for control system
-
Check t
he gate‘s partial open functio
n
The gate‘s opening width from the CLOSE position to the PartialOPEN position depends on the
configured motor runtime for the movement. Said preconfigured runtime can be changed in the
menu as follows:
-
Menu: „Settings“, „Set timer“, „Runtime PartOPEN“:
Select a greater or smaller value
(increase or reduce opening width)
-
Quit menu
-
Move the gate from the CLOSE position to the PartialOPEN position and check opening
size