Commissioning the SMC02
For operational details refer to your system specific documentation:
•
VAR4/12/20 Routers: [
Table 5-2
]
•
VAR8-ACU: [
Table 5-5
]
•
Intellevac ACU: [
Table 5-8
]
The following details are correct for the current VAR Router and Audio Control Unit (ACU)
software versions at the time of publication:
•
VAR4/12/20 Router: CP 4.1.470
•
Intellevac ACU: CP V1.5.114
•
VAR8-ACU: CP V1.5.114
If any difficulties are encountered, then refer to Application Solutions Limited for advice quoting
the software version of your system. The software version is displayed via the
Configuration
→
System
→
Misc
→
Software
menu.
Configure the SMC02 from the Router Configuration Tool or system front panel, as described in the following
sections.
5.1
Obtaining the Router’s Input Number
Check the system design documentation to find the Router’s audio input number being used for the SMC02.
This input number will be required throughout this commissioning procedure, being referred as
nn
.
Note that only Router’s inputs 1 and 2 support Fire Microphone with hardware failsafe bypass
operation in the event of processor failure.
5.2
Configuring the Microphone Type
Menu:
Configuration
Æ
System
Æ
Router
Æ
Inputs
Æ
Mic/Line
Æ
<
I/P #
nn
– MIC/LINE
nn
>
Configure the SMC02 as:
•
Zoned Fire Microphone
: for standard units (emergency microphone): SMC02F and SMC02G
•
Paging Microphone
: for ‘S’ variants units (non-emergency microphone): SMC02FS and SMC02GS
Issue: 02 complete, approved