TLK72 B

MICROPROCESSOR-BASED 

DIGITAL  

ELECTRONIC CONTROLLER

 

FOREWORD

 

This manual contains the information

 

necessary for the product to be installed

 

correctly and also instructions for its

 

maintenance and use; we therefore recommend 
that the utmost attention is paid to the

 

following instructions and to save it. 

This document is the exclusive property of Ascon Tecnologic 
S.r.l which forbids any reproduction and divulgation , even in
part, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l reserves the right to make any formal or
functional changes at any moment and without  any notice.
Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please
remember that the plant has to be equipped with additional
devices which will guarantee safety.
Ascon Tecnologic S.r.l and its legal representatives do not
assume any responsibility for any damage to people, things or
animals deriving from violation, wrong or improper use or in
any case not in compliance with the instrument’s features.

INDEX 

1

 

INSTRUMENT DESCRIPTION

 

1.1 GENERAL 

DESCRIPTION 

1.2 

FRONT PANEL DESCRIPTION 

2

 

PROGRAMMING

 

2.1 

FAST PROGRAMMING OF SET POINT 

2.2 PARAMETER 

PROGRAMMING 

2.3 

PARAMETER PROGRAMMING LEVELS 

3

 

INFORMATION ON INSTALLATION AND USE 

3.1 PERMITTED 

USE 

3.2 MECHANICAL 

MOUNTING 

3.3 ELECTRICAL 

CONNECTIONS 

3.4 

ELECTRICAL WIRING DIAGRAM 

4

 

FUNCTIONS

 

4.1 

MEASURING AND VISUALIZATION 

4.2 OUTPUTS 

CONFIGURATION 

4.3 ON/OFF 

CONTROL 

4.4 

NEUTRAL ZONE ON/OFF CONTROL 

4.5 

SINGLE ACTION PID CONTROL 

4.6 

DOUBLE ACTION PID CONTROL 

4.7 AUTOTUNING 

FUNCTION 

4.8 

REACHING OF SET POINT AT CONTROLLED SPEED 

4.9 

ALARM OUTPUT FUNCTIONS 

4.10  PARAMETERS CONFIGURATION BY A01 

5

 

PROGRAMMABLE PARAMETERS TABLE

 

6

 

PROBLEMS, MAINTENANCE AND WARRANTY

 

6.1 ERROR 

SIGNALLING 

6.2 CLEANING 
6.3 

WARRANTY AND REPAIRS 

7

 

TECHNICAL DATA

 

7.1 ELECTRICAL 

DATA 

7.2 MECHANICAL 

DATA 

7.3 

DIMENSIONS, PANEL CUT-OUT AND MOUNTING 

7.4 FUNCTIONAL 

DATA 

7.5 

MEASUREMENT RANGE TABLE 

7.6 

INSTRUMENT ORDERING CODE 

1 - INSTRUMENT DESCRIPTION 

1.1 - GENERAL DESCRIPTION

 

TLK 72 B is a digital microprocessor-based controller, with ON/OFF, 
Neutral Zone ON/OFF, PID single action, PID dual action (direct 
and reverse) control and with 

AUTOTUNING 

function (FAST or 

OSCILLATING type). 
The process value is visualized on 4 red displays, while the output 
status is indicated by 2 LED displays. 
The instrument is equipped with a 3 LED programmable shift 
indexes and can have up to 2 outputs: relay type or can drive solid 
state relays type (SSR). 
Depending on the model required the input accept: 

C

: Thermocouples temperature probes (J, K, S and Ascon 

Tecnologic ZIS Infrared sensors), mV signals (0... 50/60 mV, 12... 
60 mV), Thermoresistances PT100. 

E

: Thermocouples temperature probes (J, K, S and Ascon 

Tecnologic ZIS Infrared sensors), mV signals (0... 50/60 mV, 12... 
60 mV), Thermistors PTC and NTC. 

I

: normalized analogue signals 0/4... 20 mA 

V

: normalized analogue signals 0... 1 V, 0/1... 5 V, 0/2... 10 V 

1.2

 - 

FRONT PANEL DESCRIPTION

TLK 72 B

AT
ST

SET

Out1 Out2

=

-

+

4

3

2

1

10

7

5

6

9

11

8

Ascon Tecnologic - TLK 72 B - OPERATING INSTRUCTIONS -

 PAG. 1

OPERATING INSTRUCTIONS

1

4

/

0

4

 - 

C

ode: ISTR_M_T

L

K

72B

_

E

_0

3

_--

ASCON TECNOLOGIC S.r.l.

Viale Indipendenza 56

27029 Vigevano (PV) ITALY

TEL.:  +39 0381 69871 - FAX: +39 0381 698730 

http:\\www.ascontecnologic.com

e-mail: [email protected]

Summary of Contents for TLK72 B

Page 1: ...LE ACTION PID CONTROL 4 7 AUTOTUNING FUNCTION 4 8 REACHING OF SET POINT AT CONTROLLED SPEED 4 9 ALARM OUTPUT FUNCTIONS 4 10 PARAMETERS CONFIGURATION BY A01 5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS M...

Page 2: ...ll the operating parameters and the functioning configuration parameters ATTENTION The instrument is programmed in factory with all the parameters to exception of the Set Point SP1 and the alarm thres...

Page 3: ...screened it has to be connected to the ground with only one side We recommend that a check should be made that the parameters are those desired and that the application functions correctly before con...

Page 4: ...symmetrical hysteresis if Cont On FA The control works in the following way in the case of reverse action or heating FunC HEAt it deactivates the output when the process value reaches SP1 HSEt in case...

Page 5: ...rEG and power of the element controlled by output 1 rEG 4 7 AUTOTUNING FUNCTION All the parameters referring to the AUTOTUNING function are contained in the group rEG The AUTO TUNING function FAST or...

Page 6: ...e while it is OFF when the alarm is active but with reverse led indication led ON alarm OFF Have now access at the group AL1 and program on par OAL1 to which output the alarm signal has to be sent The...

Page 7: ...indication led on the device A01 it has to result green because if the led results green blinking or red blinking this means that on the device it has not been downloaded any valid configuration and t...

Page 8: ...Once the error has been found try to repeat the auto tuning noAt Auto tuning not finished within 12 hours Check the functioning of probe and actuator and try to repeat the auto tuning ErEP Possible an...

Page 9: ...PANEL GASKET 9 BRACKETS AT ST SET Out1 Out2 4 20 mA SEnS 4 20 0 50 mV SEnS 0 50 0 60 mV SEnS 0 60 12 60 mV SEnS 12 60 0 1 V SEnS 0 1 0 5 V SEnS 0 5 1 5 V SEnS 1 5 0 10 V SEnS 0 10 2 10 V SEnS 2 10 7 6...

Reviews: