[14] o2F - Output 2 function

Available: 

When the out2 is a relay output (hardware):

Range: nonE

  Output not used;

H.rEG

  Heating output (reverse);

c.rEG

  Cooling output (direct).

When using the servomotor control, 

both

 

Out1

 and 

Out2

 are to be selected as Heating or Cooling 

(

o2F

 = 

o3F

 = 

HrEG

 

or

 

o2F

 = 

o3F

 = 

crEG

); 

Parameter 

[39] cont

 must be set as 

3pt

.

[15] o3.AL - Alarms linked up with Out 3

Available: 

Always.

Range: 

0... 31 with the following rule:

+1

  Alarm 1;

+2

  Alarm 2;

+4

  Loop break alarm;

+8

  Sensor break (burn out);

+16

 Potentiometer break alarm.

[16] o3Ac - Out 3 action

Available: 

Always.

Range: dir

 

Direct action;

rEU

 

Reverse action;

dir.r

 

Direct action with reverse LED indication;

rEU.r

 

Reverse action with reverse LED indication.

Notes: 1.  Direct action:

 the output repeats the status of the 

driven element. 

Example:

 the output is an alarm output with direct 

action.  When the alarm switches to ON, the relay 
is energized.

2.  Reverse action:

 the output status is the opposite 

of the status of the driven element.   

Example:

 the output is an alarm output with 

reverse action.  When the alarm is OFF, the 
relay is energized.  This setting is usually named 

fail-safe

” and it is generally used in dangerous 

process in order to generate an alarm also when 
the instrument power supply goes OFF or the 
internal watchdog starts.

[17] o4.AL - Alarms linked up with Out 4

Available: 

Always.

Range: 

0... 31 with the following rule:

+1

  Alarm 1;

+2

  Alarm 2;

+4

  Loop break alarm;

+8

  Sensor break (burn out);

+16

 Potentiometer break alarm.

[18] o4Ac - Out 4 action

Available: 

Always.

Range: dir

 

Direct action;

rEU

 

Reverse action;

dir.r

 

Direct action with reverse LED indication;

rEU.r

 

Reverse action with reverse LED indication.

]

AL1 Group - Alarm 1 parameters

[19] AL1t - Alarm 1 type

Available: 

Always.

Range:  • 

When at least one output is programmed as con-
trol output:

nonE

 

Alarm not used;

LoAb

  Absolute low alarm;

HiAb

 

Absolute high alarm;

LHAo

  Absolute band alarm with alarm indication 

out of the band;

LHAi

 

Absolute band alarm with alarm indication 
inside the band;

SE.br

  Sensor break;

LodE

 

Deviation low alarm (relative);

HidE

 

Deviation high alarm (relative);

LHdo

  Relative band alarm with alarm indication 

out of the band;

LHdi

 

Relative band alarm with alarm indication 
inside the band.

• 

When no output is programmed as control output:

nonE

 

Alarm not used;

LoAb

  Absolute low alarm;

HiAb

 

Absolute high alarm;

LHAo

  Absolute band alarm with alarm indication 

out of the band;

LHAi

 

Absolute band alarm with alarm indication 
inside the band;

SE.br

  Sensor break.

Notes: 1. 

The relative and deviation alarms are “relative” to 
the operative set point value. 

LoAb

OUT

AL1

AL1

PV

HAL1

time

HiAb

off

off

off

OUT

AL1

AL1

PV

HAL1

time

off

off

off

ON

ON

ON

ON

LHAo

PV

AL1H

HAL1

time

off

off

off

LHdo

OUT

AL1

AL1L

HAL1

PV

AL1H

SP

HAL1

time

OUT

AL1

-AL1L

HAL1

off

off

off

ON

ON

ON

ON

2. 

The (SE.br) sensor break alarm will be ON when 
the display shows 

----

 indication.

[20] Ab1 - Alarm 1 function

Available: 

When [19] AL1t is different from 

nonE

.

Range: 

 0... 15 with the following rule:

+1

  Not active at power up;

+2

  Latched alarm (manual reset);

+4

  Acknowledgeable alarm;

+8

  Relative alarm not active at set point change.

Example:

 Setting Ab1 equal to 5 (1+4) the alarm 1 will be 

“Not active at power up” and “Acknowledgeable”.

Notes: 1. 

The “Not active at power up” selection allows to 
inhibit the alarm function at instrument power up 
or when the instrument detects a transfer from:

• 

Manual mode (oPLo) to Auto mode;

• 

Stand-by mode to Auto mode.

The alarm will be automatically enabled when the 
measured value reaches, for the first time, the 
alarm threshold ±hysteresis (in other words, when 
the initial alarm condition disappears).

PWR ON

AL1

PV

time

off

off

Ab1 = +1

Ab1 = +0

off

off

ON

ON

ON

Summary of Contents for KX6

Page 1: ...ng exposed terminals and wiring on the back Select a mounting location having the following characteristics 1 It should be easily accessible 2 There is minimum vibrations and no impact 3 There are no...

Page 2: ...e the 2 retainers To re insert the controller in its housing reverse the extraction procedure 2 3 General notes about wiring 1 Do not run input wires together with power cables 2 External components l...

Page 3: ...Common 24 VAC DC Notes 1 The isolated input DI2 must be used in one of the modes determined by the link High level input 110 220 VAC Low level input 24 VDC VAC 2 Logic input 2 is isolated by the meas...

Page 4: ...ot exceed 1 5 km at 9600 baud 2 7 Power Supply Power Supply 11 12 Supply Voltage 100 240 VAC 15 10 Notes 1 Before connecting the instrument to the power line make sure that line voltage is equal to th...

Page 5: ...e Temperature drift It is part of the global accuracy Operating temperature 0 50 C 32 122 F Storage temperature 30 70 C 22 158 F Humidity 20 85 RH not condensing Electromagnetic compatibility and safe...

Page 6: ...on parameters is protected by a password Note The instrument will show only the parameters consistent with the specific hardware and in accordance with the value assigned to the previous parameters e...

Page 7: ...nd the OEM parameter set has NOT been loaded 2 Using the serial link it is always possible to send to the address 13H the corretct password in order to obtain the desired action 481 for the Factory se...

Page 8: ...es automatically in MAN mode Removed the burnout condition the instrument remains in MAN mode until Auto mode is selected by OPEr parameter a command by serial link digital imput or by the key pressur...

Page 9: ...vailable Always Range When at least one output is programmed as con trol output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with alarm indication out...

Page 10: ...19 AL1t is different from SE br Range 1 9999 engineering units Notes 1 The hysteresis value is the difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the...

Page 11: ...ange and stand by LbA group Loop break alarm General note about LBA alarm The LBA operate as follows applying the 100 of the power output to a process the process variable after a time due to the proc...

Page 12: ...nditions e g set point change during tune execution etc Note Fast auto tune can start only when the measured value PV is lower than SP 1 2 SP Available When 39 cont PID or 3Pt Range 4 8 where 4 Oscill...

Page 13: ...th a power output equal to the value it will use at steady state instead of zero and the undershoot will become very little in theory equal to zero Available When 39 cont PID or 3Pt Range 100 0 100 0...

Page 14: ...rument returns at P cAL parameter 5 During the potentiometer calibration the instrument detects the real valve stroke time and stores it in the Str t Stroke time parameter At the end of the automatic...

Page 15: ...e master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local set point equal to 45 C The fourth zone has a local set point equal...

Page 16: ...of the instrument control alarms etc 81 dSPu Status of the instrument at power up Available Always Range AS Pr Starts in the same way it was prior to the power down Auto Starts in Auto mode oP 0 Start...

Page 17: ...of the configuration procedure is completed In order to exit from configuration parameter procedure proceed as follows Push button Push button for more than 10 s The instru ment will come back to the...

Page 18: ...en the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can force...

Page 19: ...no buttons for more than 10 seconds 8 4 Automatic Mode 8 4 1 Keyboard function when the instrument is in Auto mode Performs the action programmed by 75 uSrb button function during RUN TIME parameter...

Page 20: ...ped from stand by to auto modes the instrument will start automatically the alarm masking the soft start functions and the auto tune if programmed 9 ERROR MESSAGES 9 1 Out of range signals The upper d...

Page 21: ...aults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 3 Maintenance This instrument does not requires periodical recalibration and it have no con...

Page 22: ...7 SP1 SP2 selection oFF 10 diF2 Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 dir...

Page 23: ...tand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 type...

Page 24: ...r up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic res...

Page 25: ...n tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts the in...

Page 26: ...ransmitted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransm...

Page 27: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 27...

Page 28: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 28...

Reviews: