Ascon Tecnologic - KxxV - Indicators -  ENGINEERING MANUAL -V2.0 PAG. 22

]

AL2 Group - Alarm 2 (AL2) configuration

no. Param.

Description

Dec. 

Point

Values

Default

Vis. 

promo

21  AL2t

Alarm 2 type

nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break

HiAb 

A-54 

22  Ab2

Alarm 2 function

From 0 to 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm

C-0 

23  AL2L

For High and low alarms, it is the low limit of the 
AL2 threshold
For band alarm, it is low alarm threshold

dP 

-1999... AL1H (E.U.)

-1999 

A-56 

24  AL2H

For High and low alarms, it is the high limit of the 
AL2 threshold
For band alarm, it is high alarm threshold

dP 

AL2L... 9999 (E.U.)

9999 

A-57 

25  AL2

AL2 threshold

dP 

AL2L... AL2H (E.U.)

A-58 

26  HAL2

AL2 hysteresis

dP 

1... 9999 (E.U.)

A-59 

27  AL2d

AL2 delay

dP 

0 (OFF)...9999  (s)

oFF 

C-0 

28  AL2o

Alarm 2 enable at out of range indication

No = Alarm NOT running when out-of-range
YES = Alarm enabled when out-of-range

no 

C-0 

]

AL3 Group - Alarm 3 (AL3) configuration

no. Param.

Description

Dec. 

Point

Values

Default

Vis. 

promo

29  AL3t

Alarm 2 type

nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break

nonE

C-0

30  Ab3

Alarm 2 function

From 0 to 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm

0

C-0

31  AL3L

For High and low alarms, is the low limit of the AL3 threshold
For band alarm, it is low alarm threshold

dP 

-1999... AL3H (E.U.)

-1999

C-0

32  AL3H

For High and low alarms, is the high limit of the AL3 threshold
For band alarm, it is high alarm threshold

dP 

AL3L... 9999 (E.U.)

9999

C-0

33  AL3

AL3 threshold

dP 

AL3L... AL3H (E.U.)

0

C-0

34  HAL3

AL3 hysteresis

dP 

1... 9999 (E.U.)

1

C-0

35  AL3d

AL3 delay

dP 

0 (OFF)...9999  (s)

oFF

C-0

36  AL3o

Alarm 3 enable at out of range indication

No = Alarm NOT running when out-of-range
YES = Alarm enabled when out-of-range

no

C-0

]

AL4 Group - Alarm 4 (AL4) Configuration

no. Param.

Description

Dec. 

Point

Values

Default

Vis. 

promo

37  AL4t

Alarm 4 type

nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break

nonE

C-0

38  Ab4

Alarm 4 function

From 0 to 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm

0

C-0

39  AL4L

For High and low alarms, it is the low limit of the AL4 threshold
For band alarm, it is low alarm threshold

dP 

-1999... AL4H (E.U.)

-1999

C-0

40  AL4H

For High and low alarms, it is the high limit of the AL4 threshold
For band alarm, it is high alarm threshold

dP 

AL4L... 9999 (E.U.)

9999

C-0

41  AL4

AL4 threshold

dP 

AL4L... AL4H (E.U.)

0

C-0

42  HAL4 AL4 hysteresis

dP 

1... 9999 (E.U.)

1

C-0

43  AL4d

AL4 delay

dP 

0 (OFF)...9999 (s)

oFF

C-0

44  AL4o

Alarm 4 enable at out of range indication

No = Alarm NOT running when out-of-range
YES = Alarm enabled when out-of-range

no

C-0

]

TIN Group - Timer Configuration

Summary of Contents for 3 V Series

Page 1: ...1 2 3 4 5 6 7 8 9 10 11 12 Prg Out1 Out2 Out3 70 27 21 12 84 45 60 2 CONNECTIONS 2 1 Connection Diagrams 2 1 1 K31 V Series 1 2 3 4 5 6 12 11 10 9 8 7 13 14 15 16 17 18 19 24 22 21 20 23 OUT4 O UT3 O...

Page 2: ...ith the instrument specifications 20 to 85 Lo strumento pu essere montato su un pannello con uno spessore massimo di 15 mm Per ottenere la massima protezione frontale IP65 neces sario montare la guarn...

Page 3: ...hort circuit Internal auxiliary PWS 10 VDC 10 20 mA max 3 3 Output Safety notes To avoid electrical shock connect power line at last For supply connections use No 16 AWG or larger wires rated for at l...

Page 4: ...ables Use an external dry contact capable to switch 0 5 mA 5 VDC The instrument needs 150 ms to recognize a contact sta tus variation The logic inputs are NOT isolated by the measuring input A double...

Page 5: ...5 mm2 or from AWG 22 to AWG 14 with connection diagrams Dimensions K3xV 78 x 35 x 64 mm 3 07 x 1 38 x 2 52 K4xV 48 x 48 x 98 mm 1 77 x 1 77 x 3 86 K85V 70 x 84 x 60 mm 2 76 x 3 31 x 2 37 Mount cut out...

Page 6: ...Output 1 R Relay SPDT 8A AC1 resistive load O VDC for SSR Output 2 Not available R Relay SPDT 8A AC1 resistive load O VDC for SSR 5 3 K48V Model K48V Front panel mounting Indicator 48 x 48 mm Power S...

Page 7: ...030 It is always possible to end manually the parameter configuration procedure see the next paragraph 3 During parameter modification the instrument con tinue to perform the control In certain condit...

Page 8: ...lable Always Range When 2 SenS Linear input 0 to 3 When 2 SenS different from linear input 0 or 1 Note Every change of the dP parameter setting will produce a change of the parameters related with it...

Page 9: ...output repeats the digital input 1 status diF 2 The output repeats the digital input 2 status Notes 1 When two or more outputs are programmed in the same way these outputs will be driven in parallel 2...

Page 10: ...bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range burn out Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates...

Page 11: ...arm 23 AL1t HiAb Absolute high alarm 23 AL1t LodE Deviation low alarm relative 23 AL1t LidE Deviation high alarm relative Range From 25 AL1L to 26 AL1H E U 28 HAL1 Alarm 1 hysteresis Available When 23...

Page 12: ...arm it is the high alarm threshold Available When 30 AL3t is different from nonE or 39 AL3t is different from SE br Range From 41 AL3L to 9999 E U 43 AL3 Alarm 3 threshold Available When 39 AL3t LoAb...

Page 13: ...mmetrical oscillator with start in ON Start OUT ON off Tr t2 off Tr t1 Tr t1 Tr t2 off Tr t1 Tr t2 Reset ON ON Notes 1 The instrument can receive the start hold and reset commands by U button by logic...

Page 14: ...push the button The display will show zero and the new readout range becomes 30 70 r P0P For the instruments with normalized signals input it is possible to set the zero value and contemporarily re se...

Page 15: ...P and AH P is equal to 10 Engineering Units 72 AL o Adjust Low Offset Available Always Range From 300 to 300 E U Example Environmental chamber with an operative range from 10 to 100 C 1 Insert in the...

Page 16: ...w alternately PASS and 0 3 By and button set a password equal to 81 4 Push button The instrument will show the acronym of the first configu ration parameter group inP 5 By button select the group of t...

Page 17: ...button in order to memorize the new value and go to the next parameter 8 When you want to come back to the standard display push the button for more than 5 seconds 8 3 How to see but not modify the Li...

Page 18: ...nt has to be equipped with additional safety devices 10 2 Warranty and Repairs This product is under warranty against manufacturing de fects or faulty materials that are found within 18 months from de...

Page 19: ...store a complete instrument configuration and to use it for other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer from a PC to an instrume...

Page 20: ...d Peaks reset t rHr Timer Run Hold Reset transition t run Timer Run transition t rES Timer reset transition t rH Timer run hold Status uP du Digital inputs in parallel to the and keys OFF A 13 diF2 Di...

Page 21: ...lure indicator bo PF Out of range burn out and Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates the digital input 2 status AL A 24 11 o4AL Alarms...

Page 22: ...4 Acknowledgeable alarm 0 C 0 31 AL3L For High and low alarms is the low limit of the AL3 threshold For band alarm it is low alarm threshold dP 1999 AL3H E U 1999 C 0 32 AL3H For High and low alarms i...

Page 23: ...Interface Configuration no Param Description Dec Point Values Default Vis promo 50 PAS2 Password level 2 0 From 0 oFF to 999 oFF Level 2 not protected by psw 20 A 93 51 PAS3 Password level 3 0 From 3...

Page 24: ...ours nonE A 97 58 h Job Threshold of the worked hours days 0 From 0 oFF to 9999 days hours oFF A 100 CAL Group User Calibration Parameters Configuration no Param Description Dec Point Values Default V...

Reviews: