background image

Ascon Tecnologic - K__V - Indicators  -  ENGINEERING MANUAL  -  PAG. 17

8.  OPERATIVE MODES

As we said at paragraph 4.1, when the instrument is powe-
red, it starts immediately to work according to the memori-
zed parameter value.

8.1  How to enter the “Operator Level”

The instrument is showing the “standard display”.

1. 

Press the 

 button 

2. 

The instrument will show alternately the acronym of the 
first parameter promoted to this level and its value.

3. 

By 

 and 

 buttons assign to this parameter the desi-

red value.

4. 

Press the 

 button in order to memorize the new value 

and go to the next parameter.

5. 

When you want to come back to the “standard display” 
push the 

 button for more than 5 seconds.

Note: 

The parameter modification of the Operator level 
is subject to a time out.  If no button is pressed for 
more than 10 seconds, the instrument goes back to 
the “standard display” and the new value of the last 
selected parameter will be lost.

8.2  How to enter the “Limited Access 

Level”

The instrument is showing the “standard display”.

1. 

Press the 

 button for more than 5 seconds;

2. 

The display will show alternately “PASS” and “0”;

3. 

By 

 and 

 buttons set the value assigned to  

[114] PAS2 (Level 2 password).

Notes: 1. 

The factory default password for configuration 
parameters is equal to 20.

2. 

All parameter modification are protected by a 
time out. If no button is pressed for more than 10 
second the instrument comes automatically back 
to the Standard display, the new value of the last 
selected parameter is lost and the parameter 
modification procedure is closed.
When you desire to remove the time out (e.g. for 
the first configuration of an instrument) you can 
use a password equal to 1000 plus the program-
med password (e.g. 1000 + 20 [default] = 1020).
It is always possible to manually End the parame-
ter configuration procedure (see below). 

4. 

Push 

 button.

5. 

The instrument will show alternately the acronym of the 
first parameter promoted to this level and its value.

6. 

By 

 and 

 buttons assign to this parameter the desi-

red value.

7. 

Press the 

 button in order to memorize the new value 

and go to the next parameter.

8. 

When you want to come back to the “standard display” 
push the 

 button for more than 5 seconds.

8.3  How to see but not modify the 

“Limited Access Parameters”

Sometime it is necessary to give to the operator the possibi-
lity to see the value assigned to the parameter promoted in 
the Limited Access level but it is important that all changes 
are made by autorized personnel only.
In this cases, proceed as follows:

1. 

Press the 

 button for more than 5 seconds

2. 

The display will show alternately “

PASS

” and “

0

”.

3. 

By 

 and 

 buttons set the value -181.

4. 

Push 

 button.

5. 

The instrument will show alternately the acronym of the 
first parameter promoted to the level 2 and its value.

6. 

Using 

 button it is possible to see the value assigned 

to all parameter present in level 2 but it will not be possi-
ble to modify it.

7. 

It is possible to come back to the “standard display” by 
pushing the 

 button for more than 3 seconds or by 

pushing no pushbutton for more than 10 seconds. 

8.3.1  Keyboard function when the instrument 

is in display mode

 

Runs the action programmed by [116] uSrb  
(

 button function during RUN TIME) parameter.

 

Allows entry into parameter modification procedures.

 

Allows you to start the “Direct set point modification” 
function (see below).

 

Allows you to display the “additional informations” (see 
below).

8.3.2  Additional informations

This instrument is able to show you some additional informa-
tions that can help you to manage your system.
The additional information is related to how the instrument is 
programmed, hence in many cases, only part of this informa-
tion is available.

1. 

When the instrument is showing the “standard display” 
push  

 button.

The display will show the maximum measured value and 
turn ON the “UP” LED

320.5.

UP LED

DOWN LED

Delta LED

2. 

Push 

 button again.  The display will show the mini-

mum measured value and turn ON the “down” LED

3. 

Push 

 button again.  The display will show the differen-

ces between the maximum and the minimum measured 
value and turn ON the “delta” LED.

4. 

Push 

 button again.  The display will show:

- “

h

” followd by the worked hours or

- “

d

” followed by the worked days

according to the [67] co.tY parameter setting.

Summary of Contents for 3 V Series

Page 1: ...1 2 3 4 5 6 7 8 9 10 11 12 Prg Out1 Out2 Out3 70 27 21 12 84 45 60 2 CONNECTIONS 2 1 Connection Diagrams 2 1 1 K31 V Series 1 2 3 4 5 6 12 11 10 9 8 7 13 14 15 16 17 18 19 24 22 21 20 23 OUT4 O UT3 O...

Page 2: ...ith the instrument specifications 20 to 85 Lo strumento pu essere montato su un pannello con uno spessore massimo di 15 mm Per ottenere la massima protezione frontale IP65 neces sario montare la guarn...

Page 3: ...hort circuit Internal auxiliary PWS 10 VDC 10 20 mA max 3 3 Output Safety notes To avoid electrical shock connect power line at last For supply connections use No 16 AWG or larger wires rated for at l...

Page 4: ...ables Use an external dry contact capable to switch 0 5 mA 5 VDC The instrument needs 150 ms to recognize a contact sta tus variation The logic inputs are NOT isolated by the measuring input A double...

Page 5: ...5 mm2 or from AWG 22 to AWG 14 with connection diagrams Dimensions K3xV 78 x 35 x 64 mm 3 07 x 1 38 x 2 52 K4xV 48 x 48 x 98 mm 1 77 x 1 77 x 3 86 K85V 70 x 84 x 60 mm 2 76 x 3 31 x 2 37 Mount cut out...

Page 6: ...Output 1 R Relay SPDT 8A AC1 resistive load O VDC for SSR Output 2 Not available R Relay SPDT 8A AC1 resistive load O VDC for SSR 5 3 K48V Model K48V Front panel mounting Indicator 48 x 48 mm Power S...

Page 7: ...030 It is always possible to end manually the parameter configuration procedure see the next paragraph 3 During parameter modification the instrument con tinue to perform the control In certain condit...

Page 8: ...lable Always Range When 2 SenS Linear input 0 to 3 When 2 SenS different from linear input 0 or 1 Note Every change of the dP parameter setting will produce a change of the parameters related with it...

Page 9: ...output repeats the digital input 1 status diF 2 The output repeats the digital input 2 status Notes 1 When two or more outputs are programmed in the same way these outputs will be driven in parallel 2...

Page 10: ...bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range burn out Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates...

Page 11: ...arm 23 AL1t HiAb Absolute high alarm 23 AL1t LodE Deviation low alarm relative 23 AL1t LidE Deviation high alarm relative Range From 25 AL1L to 26 AL1H E U 28 HAL1 Alarm 1 hysteresis Available When 23...

Page 12: ...arm it is the high alarm threshold Available When 30 AL3t is different from nonE or 39 AL3t is different from SE br Range From 41 AL3L to 9999 E U 43 AL3 Alarm 3 threshold Available When 39 AL3t LoAb...

Page 13: ...mmetrical oscillator with start in ON Start OUT ON off Tr t2 off Tr t1 Tr t1 Tr t2 off Tr t1 Tr t2 Reset ON ON Notes 1 The instrument can receive the start hold and reset commands by U button by logic...

Page 14: ...push the button The display will show zero and the new readout range becomes 30 70 r P0P For the instruments with normalized signals input it is possible to set the zero value and contemporarily re se...

Page 15: ...P and AH P is equal to 10 Engineering Units 72 AL o Adjust Low Offset Available Always Range From 300 to 300 E U Example Environmental chamber with an operative range from 10 to 100 C 1 Insert in the...

Page 16: ...w alternately PASS and 0 3 By and button set a password equal to 81 4 Push button The instrument will show the acronym of the first configu ration parameter group inP 5 By button select the group of t...

Page 17: ...button in order to memorize the new value and go to the next parameter 8 When you want to come back to the standard display push the button for more than 5 seconds 8 3 How to see but not modify the Li...

Page 18: ...nt has to be equipped with additional safety devices 10 2 Warranty and Repairs This product is under warranty against manufacturing de fects or faulty materials that are found within 18 months from de...

Page 19: ...store a complete instrument configuration and to use it for other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer from a PC to an instrume...

Page 20: ...d Peaks reset t rHr Timer Run Hold Reset transition t run Timer Run transition t rES Timer reset transition t rH Timer run hold Status uP du Digital inputs in parallel to the and keys OFF A 13 diF2 Di...

Page 21: ...lure indicator bo PF Out of range burn out and Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates the digital input 2 status AL A 24 11 o4AL Alarms...

Page 22: ...4 Acknowledgeable alarm 0 C 0 31 AL3L For High and low alarms is the low limit of the AL3 threshold For band alarm it is low alarm threshold dP 1999 AL3H E U 1999 C 0 32 AL3H For High and low alarms i...

Page 23: ...Interface Configuration no Param Description Dec Point Values Default Vis promo 50 PAS2 Password level 2 0 From 0 oFF to 999 oFF Level 2 not protected by psw 20 A 93 51 PAS3 Password level 3 0 From 3...

Page 24: ...ours nonE A 97 58 h Job Threshold of the worked hours days 0 From 0 oFF to 9999 days hours oFF A 100 CAL Group User Calibration Parameters Configuration no Param Description Dec Point Values Default V...

Reviews: