Ascon Tecnologic - K__V - Indicators - ENGINEERING MANUAL - PAG. 9
[9] diF1 - Digital input 1 function
Available:
When the instrument is equipped with digital inputs.
Range:
oFF = No function.
AAC = Alarm Reset [status]
ASi = Alarm acknowledge (ACK) [status].
HoLd = Hold of the measured value [status].
r.Pic = Peaks reset [transition]
0.Pot = start of the 0.Pot procedure. [transition]
r.PoP = Start of the 0.Pot procedure and Peaks
reset [transition]
t.rHr = Timer Run/Hold/Reset [transition]
t.run = Timer Run [transition] a short closure al-
lows to start timer execution.
t.rES = Timer rese [transition] a short closure
allows to reset timer count.
t.rH = Timer run/hold [Status]
- Contact closure = timer RUN
- contact opend = timer Hold
uP.du = Digital input 1 will work in parallel to the
button while digital input 2 will work in
parallel to the
button.
[10] diF2 - Digital input 2 function
Available:
When the instrument is equipped with digital inputs.
Range:
oFF = No function
AAC = Alarm Reset [status]
ASi = Alarm acknowledge (ACK) [status].
HoLd = Hold of the measured value [status].
r.Pic = Peaks reset [transition]
0.Pot = start of the 0.Pot procedure. [transition]
r.PoP = Start of the 0.Pot procedure and Peaks
reset [transition]
t.rHr = Timer Run/Hold/Reset [transition]
t.run = Timer Run [transition] a short closure al-
lows to start timer execution.
t.rES = Timer rese [transition] a short closure
allows to reset timer count.
t.rH = Timer run/hold [Status]
- Contact closure = timer RUN
- contact opend = timer Hold
uP.du = Digital input 1 will work in parallel to the
button while digital input 2 will work in
parallel to the
buttons.
Note:
When
diF1
is equal to
uP.du
,
diF2
setting is forced
to
uP.du
and
diF2
value and cannot perform another
additional function.
]
out group -
Output parameters
[11] o1F - Out 1 function
Available:
Always.
Range:
nonE = Output not used. With this setting the status
of the this output can be driven directly
from serial link
AL = Alarm output
t.out = Timer output
t.HoF = Timer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out, Power failure indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
Notes: 1.
When two or more outputs are programmed in the
same way, these outputs will be driven in parallel.
2.
The power failure indicator will be reset when the
instrument detect an alarm reset command by
key, digital input or serial link.
[12] o1.AL - Alarms linked up with the out 1
Available:
When [11] o1F = AL
Range:
0... 15 with the following rule:
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Alarm 4
+ 16 = Sensor break (burn out)
Example 1:
Setting 3 (2+1) the output will be driven by the
alarm 1 and 2 (OR condition).
Example 2:
Setting 13 (8+4+1) the output will be driven by
alarm 1 + alarm 3 + alarm 4.
[13] o1Ac - Output 1 action
Available:
When [11] o1F is different from “
nonE
”
Range:
dir =
Direct action
rEU = Reverse action
dir.r = Direct action with revers LED indication
rEU.r = Reverse action with reverse LED indication.
Notes: 1.
- Direct action: the output repeats the status of
the driven element.
Example:
the output is an alarm output with
direct action. When the alarm is ON, the relay will
be energized (logic output 1).
2.
Reverse action: the output status is the opposite
of the status of the driven element.
Example:
the output is an alarm output with
reverse action. When the alarm is OFF, the relay
will be energized (logic output 1). This setting is
usually named “fail-safe” and it is generally used
in dangerous process in order to generate an
alarm when the instrument power supply goes
OFF or the internal watchdog starts.
[14] o2F - Out 2 function
Available:
When the instrument has out 2 option.
Range:
nonE = Output not used. With this setting the status
of the this output can be driven directly
from serial link.
AL =
Alarm output
t.out = Timer output
t.HoF = Timer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out, Power failure indicator
diF.1 = The output repeates the digital input 1 status
diF.2 = The output repeates the digital input 2 status
St.By = Stand By status indicator
Note:
For other details see [11] O1F parameter
[15] o2.AL – Alarms linked up with Out 2
Available:
When [14] o2F = AL
Range:
0... 15 with the following rule:
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Alarm 4
+ 16 = Sensor break (burn out)
Note:
For more details see [13] o1.AL parameter