background image

Temp.

off

ON

SP 

time

r.d

off

off

off

ON

ON

Pr1

Out

(ot)

Second control (par. 

“P.P2”

 )  foresees an inhibition to the

activation of the output  by a time delay that starts when the output
is turning off (delay after switching-off).

ON

off

P.P2

P.P2

P.P2

SP 

Temp.

time

r.d

ON

ON

off

off

Pr1

Out

(ot)

Third control (par. 

“P.P3”

 ) foresees an inhibition to the activation

of the output by a time delay that starts when the output was
turning on last time (delay between switching-on).

P.P3

off

SP 

ON

Temp.

P.P3

P.P3

time

r.d

off

off

ON

ON

Pr1

(ot)

Out

During the output inhibition  the led OUT (Cool o Heat) blinking.
It is also possible to prevent activation of the output after the
instrument is turned on, for the time set in the parameter 

“P.od”

.

During the power on delay phase, the display shows the indication

od,

 alternating with the normal visualisation.

All the functions are disabled by relative parameters =  oF.

4.8 - DEFROST CONTROL

The defrosting control acts on the outputs configured as “ot” and
“dF”

.

The type of defrosting that the instrument must carry out is set by
the parameter 

“d.dt”

 that can be programmed:

= EL

 - WITH ELECTRICAL HEATING  (or BY STOPPING

COMPRESSOR): during defrosting, the output “ot” is deactivated
while the output “dF” is enabled.
The defrost will be by Stopping compressor if  not using the “dF”
output

= in

 - WITH HOT GAS or INVERSION OF CYCLE:

during defrosting the outputs “ot” and “dF” are enabled

= no

 - WITHOUT COMPRESSOR OUTPUT CONDITIONING:

during defrosting, the output “ot” continuous to operate in order to
temperature controller while the output “dF” is enabled.

= Et

 -  WITH ELECTRICAL HEATING AND DEFROSTING

TEMPERATURE CONTROL: during defrosting, the output “ot” is
deactivated while the output “dF” operate as evaporator
temperature control. In this mode the defrost lenght is by time-out   
(time "d.dE").  During the defrost "dF" output  it behaves as an
heating mode temperature control  with Set = "d.tE" and fixed
differential at 1°C and operate in order to evaporator probe (EP).

4.8.1 -  AUTOMATIC DEFROST

 

STARTS

The automatic control of defrost  occours by interval times.
The automatic defrost function is activate when at the parameter

“d.di”

 is set the defrost interval time.

The first defrost after swiching on can be set by par. 

“d.Sd”

This allows to perform the first defrost to a different interval from
"d.di." time.
If it is desired that to every instrument power on a defrost cycle is
realized (as long as the conditions set in the parameters “d.tS” and
"d.tE" apply) program the par. "d.Sd" = oF.
This allows the evaporator to be permanently defrosted, even when
 frequent interruptions to power supply occur that may cause the
cancellation of the various defrosting cycles.
Instead

 

if is desired all defrost to the same interval program "d.Sd"

= "d.di."
Automatic defrost function is disable when  “d.di” = oF.
Counting mode interval  and automatic defrost starts is set through
the parameter 

"d.dC"

 that can be programmed:

= rt

 - intervals with counts the total function time (instrument on)

This mode results that currently used in the refrigerators systems.

= ct

 - intervals with counts only the compressor function time

(output “ot” switched on)
Mode typically used in the positive temperature refrigerators
system with defrost by stopping compressor.

= cS

 - the instrument carries out a defrosting cycle at each

compressor stop (i.e. at each deactivation of the output “ot”) or
however at defrost interval end with counts the total function time
(instrument on).
If "d.di" = oF the defrost happens only to the compressor stop.
This mode is used only on particular refrigerator system in which is
desired to always have the evaporator to the maximum efficiency
conditions every compressor cycle.

= St

 - Defrost for evaporator temperature. The instrument starts a

defrost cycle when the temperature evaporator (“EP” probe) goes
below the “d.tS” programmed temperature or however at defrost
interval end with counts the total function time (instrument on).
If "d.di" = oF the defrost happens only when the evaporator
temperature goes below“d.tS” temperature.
This system can be used in heat pump defrost system (in this case
the defrosting intervals  are usually disabled) or to guarantee a
defrost if the evaporator reaches very low temperatures that
normally result symptomatic of a bad thermal exchange in
comparison to the normal working conditions.

= dd

 - "DYNAMIC DEFROST INTERVALS SYSTEM". This mode

allows to dynamically reduce in progress the defrost interval
counting ("d.di" or "d.Sd" if is the first defrost), anticipating so the
execution of a defrost when it was necessary, in order to an
algorithm that allows to notice a decrease performances of  
refrigerator thermal exchange.  
Besides it maintains activates the mode "St" that it allows a further
possibility of control of the defrost in order to notice a decrease
performances of  refrigerator thermal exchange.
The algorithm allows to esteem a reduction of  thermal exchange in
base to the increase of the difference of temperature between Pr1
(controlled temperature) and evaporator (“EP” probe) that is memo-
rized by the instrument in proximity of the Set Point.  
The advantage of the “Dynamic Defrost Interval” is the possibility to
program a defrost interval time more longer than normal.
The instrument will have the possibility to anticipate the defrost if
necessary or to start the cycle after the programmed time.
If the system results set correctly  is possible to to avoid many non
necessary defrosting cycles (and therefore to obtain an energy sa-
ving) that could instead happens in the normal operation when, to
guarantee with greater certainty the system efficency , the defrost
interval is programmed at a too low time.
In addition to normal defrost parameters the “Dynamic Defrost
Intervals System”, it foresees the parameter:

“d.dd”

 - DEFROST INTERVAL PERCENTAGE REDUCTION. It

allows to establish the percentage of reduction of the remaining
time to start defrost when the conditions for the reduction happen.  
If par. "d.dd" = 100% at the first increase of the memorized diffe-
rence of temperature between cell (Pr1) and evaporator (> 1 °) a
defrost start immediately

ASCON TECNOLOGIC - Z31Y 

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/12 -  ISTR-MZ31YENG02 -  PAG. 6

Summary of Contents for Z31SY

Page 1: ...4 10 1 ALARM FUNCTIONS 4 10 EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCT...

Page 2: ...status on off off and silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROG...

Page 3: ...identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring the air and product temperature for the transport storage and distr...

Page 4: ...nt is switched off peak values are always re set However it is also possible to reset these values if the instrument is switched on by using the DOWN key hold for 3 sec during peak visualization The d...

Page 5: ...put will be on in normal mode Set Point SP active and off in economy mode operation Set Point SP2 active 4 Internal Light output managed by digital input This output will be on when door is opened i F...

Page 6: ...lts that currently used in the refrigerators systems ct intervals with counts only the compressor function time output ot switched on Mode typically used in the positive temperature refrigerators syst...

Page 7: ...1 differential Hysteresis The active defrost is shown on the instrument display with the lighting up of the DEFROST led At the end of defrosting it is possible to delay the new start up of the compre...

Page 8: ...s the alarm signal when the alarm status ends To cancel the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory An or An it is necessary...

Page 9: ...cessary that the device or instrument are being supplied USB SUPPLY AC SUPPLY SUPPLY ADAPTER 12 VDC USB For additional info please have a look at the A01 instruction manual 4 12 2 TVRY REMOTE DISPLAY...

Page 10: ...obe Calibration i C2 10 oF oF 0 01 9 59 min sec Fan delay after defrost F Fd 37 oF oF on Fan status during defrost F FE 36 1 0 0 0 30 0 C F Differential fan control F dF 35 99 9 99 9 999 C F Low tempe...

Page 11: ...rs relative to compressor protection and power on delay 99 5 min sec x10 1 0 255 MODBUS Station address for serial communication t AS 60 oF oF 999 Access Password to parameter functions t PP 59 oF oF...

Page 12: ...21 990 25 C or NTC 103AT 2 10K 25 C 1 digital input for free voltage contacts alternative to Pr2 input Output s up to 2 relay outputs 5 A Res 6 4 A 8 3 A Out2 SPDT 8A 1 2HP 250V 1 3HP 125 VAC 12 A Res...

Page 13: ...1000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C...

Reviews: