Ascon tecnologic Z31SY Operating Instructions Manual Download Page 4

avoid malfunctioning that may cause irregularities in the plant that
could cause damage to people, things or animals.

3.4 - ELECTRICAL WIRING DIAGRAM

Dig.

SUPPLY

Z31Y

1

SPDT

NO

4

3

2

6 7

5

OUT1

NC

C

C

Pr1 Pr2

INPUTS

9

8

10

OUT2

NO

NC

11 12

NO

SPST-NO

C

(12 A MAX for extr. conn. model)

Out2:

Out1:

6 A Res.

6 (4) A

8 (3) A

5 FLA

30 LRA

12 A Res.

60730

EN

16 (9) A

61810

EN

10 (4) A

UL

INTERNAL

BUZZER

4 - FUNCTIONS

4.1 - ON / STAND-BY

 

FUNCTION

The instrument, once powered up, can assume 2 different
conditions:
- ON : means that the controller uses the control functions.
- STAND-BY : means that the controller does not use any control
function and the display is turned off except for the  Stand-by led.
If there is no power, and then power returns, the system always
sets itself in the condition it was in before the  black-out.
The ON/Stand-by function can be selected: 
- Pressing the key U for at least 1 sec. if the parameter 

"t.UF"

 = 4.

-Pressing the key DOWN/AUX for at least 1 sec. if the parameter

"t.Fb"

 = 4.

- using the digital input if the parameter 

“i.Fi”

 = 10

4.2 - MEASURING AND VISUALIZATION

Via the parameter 

“i.SE”

 it is possible to select the type of probes

that one wishes to use and which can be: thermistores PTC
KTY81-121 (

Pt

) or NTC 103AT-2 (

nt

).

Via the parameter 

“i.uP”, 

 it is possible to select the temperature

unit of measurement the desired measurement resolution (

C0

=°C /

1° ; 

C1

=°C / 0.1° ; 

F0

= °F / 1°; 

F1

= °F / 0.1°).

The instrument allows the measuring to be calibrated, that can be
used for re-calibrating the instrument according to application
needs, through the parameters 

“i.C1”

 (for the input Pr1) and

“i.C2” 

(for the input Pr2).

The functions carried out by Pr2 probe is defined by the parameter

“i.P2”

.

This parameter can be configured for the following functions:

= EP

 - Evaporator probe: used to managing the defrost and the  

evaporator fans (see relative functions)

= Au

 - Auxiliary probe 

= dG

 - Digital input (see Digital input functions)

If probe Pr2 is not used, set the relative parameter 

“i.P2”

= oF.

Using the parameter

 “i.Ft”, 

it is possible to set the time constant

for the software filter for measuring the input values to be able to
reduce the sensitivity to measurement disturbances (increasing the
time).
Through the parameter 

“i.dS”,

 it is possible to fix the normal

visualisation on the display that can be the measurement of the
probe Pr1 (P1), the measurement of the probe Pr2 (P2), the active
set point value (SP), or it can have the numerical display switched
off (oF).
Through the parameter 

“i.CU”,

 it is possible to program an measu-

re offset that will be applied to the temperature show on the display
(only if  i.dS”= P1, P2).
All the controls will always happen in operation of the measure
corrected only by the calibration parameters (“i.C1”, “i.C2”).

The normal visualisation on the display  is established by par.
“i.dS”, but it is possible to visualise all the variables and the highest
and lowest Pr1 peak  measurement values in rotation by quickly
pressing and releasing key U.
The display will alternately show the code that identifies the
variable and its value.
The variable are:

“Pr1”

 - Pr1 temperature

“Pr2”

 - Pr2 temperature ( on/oF state if is progr. as  digital input )

Lt”

  and the lowest Pr1 peak temperature

“Ht

” and the highest Pr1 peak temperature

When the instrument is switched off, peak values are always
re-set. However, it is also possible to reset these values if the
instrument is switched on by using the DOWN key hold for 3 sec.
during peak visualization.
The display will show “---” and peaks memory will be reset.
The exit of this visualisation mode occurs automatically 15 seconds
after the last pressing on the key U.
Please remember that visualisation of the Pr1 probe can be
changed by the defrosting  display lock function, by using the
parameter 

“d.dL”

 (see defrost function).

4.3 - DIGITAL INPUT

The digital input present on the instrument, alternative to Pr2
probe,  accepts free voltage contacts, the function carried out is
defined by the parameter 

“i.Fi”

 and the action can be delayed for

the time set in parameter 

“i.ti”.

If digital input is used, set the input relative parameter  “i.P2” = dG.
The parameter “i.Fi” can be configured for the following functions:

= 0

 - No function

= 1

 - Defrosting start command with contact normally open: on  

closing the digital input 1 (and after the “i.ti” time) a defrosting cycle
is activated.

= 2

 - Defrosting end command with contact normally open: on  

closing the digital input 1 (and after the “i.ti” time) a defrosting cycle
is ended if in progress or defrosting is inhibited.

= 3

 - continuous cycle activation command with contact normally

open: on  closing the digital input (and after the “i.ti” time) a
continuous cycle is started up as described in the paragraph on the
continuous cycle function.

= 4

 - External alarm signal with contact normally open: on  closing

the digital input (and after the “i.ti” time) the alarm is activated and
the instrument visualises 

AL

 and the variable set in parameter

“i.dS” alternately on the display.

= 5

 -Cell door opening with fan stop with contact normally open: on

closing the digital input (and after the “i.ti” time) the fans are
stopped and the instrument visualises 

oP

 and the variable set in

parameter “i.dS” alternately on the display. With this function mode,
the action of the digital input also activates the time that can be set
in parameter "A.oA" after which the alarm is activated to signal that
the door has been left open and the fa n restart.

= 6

 - Cell door opening with compressor and fan stop with contact

normally open: similar to “i.Fi” = 5 but with fan and compressor
stop. At the intervention of the door open alarm alarm compressor
and fan restarts.

= 7

 - Remote control of auxiliary output AUX with contact normally

open: on  closing the digital input (and after the “i.ti” time) the
auxiliary output is activated as described in the  "i.Fo" = 2 function
mode of the auxiliary output.

= 8

 - Selecting the active set point (SP/SP2) with contact normally

open: on  closing the digital input (and after the “i.ti” time) the
temperature set point “SP2” is activated. When instead the input is
open the set point “SP” is active.

= 9

 - Signalling of external alarm with disablement of all the control

outputs with contact normally open: on  closing the digital input
(and after the “i.ti” time) all the control outputs are disabled, the
alarm is activated and the instrument visualises  

AL

 and the

variable set in  parameter “i.dS” alternately on the display.

= 10

 - Switching on/switching off (Stand-by) of instrument with

contact normally open: on  closing the digital input (and after the
“i.ti” time) the instrument is switched on while it is placed in
Stand-by when opened.

ASCON TECNOLOGIC - Z31Y 

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/12 -  ISTR-MZ31YENG02 -  PAG. 4

Summary of Contents for Z31SY

Page 1: ...4 10 1 ALARM FUNCTIONS 4 10 EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCT...

Page 2: ...status on off off and silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROG...

Page 3: ...identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring the air and product temperature for the transport storage and distr...

Page 4: ...nt is switched off peak values are always re set However it is also possible to reset these values if the instrument is switched on by using the DOWN key hold for 3 sec during peak visualization The d...

Page 5: ...put will be on in normal mode Set Point SP active and off in economy mode operation Set Point SP2 active 4 Internal Light output managed by digital input This output will be on when door is opened i F...

Page 6: ...lts that currently used in the refrigerators systems ct intervals with counts only the compressor function time output ot switched on Mode typically used in the positive temperature refrigerators syst...

Page 7: ...1 differential Hysteresis The active defrost is shown on the instrument display with the lighting up of the DEFROST led At the end of defrosting it is possible to delay the new start up of the compre...

Page 8: ...s the alarm signal when the alarm status ends To cancel the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory An or An it is necessary...

Page 9: ...cessary that the device or instrument are being supplied USB SUPPLY AC SUPPLY SUPPLY ADAPTER 12 VDC USB For additional info please have a look at the A01 instruction manual 4 12 2 TVRY REMOTE DISPLAY...

Page 10: ...obe Calibration i C2 10 oF oF 0 01 9 59 min sec Fan delay after defrost F Fd 37 oF oF on Fan status during defrost F FE 36 1 0 0 0 30 0 C F Differential fan control F dF 35 99 9 99 9 999 C F Low tempe...

Page 11: ...rs relative to compressor protection and power on delay 99 5 min sec x10 1 0 255 MODBUS Station address for serial communication t AS 60 oF oF 999 Access Password to parameter functions t PP 59 oF oF...

Page 12: ...21 990 25 C or NTC 103AT 2 10K 25 C 1 digital input for free voltage contacts alternative to Pr2 input Output s up to 2 relay outputs 5 A Res 6 4 A 8 3 A Out2 SPDT 8A 1 2HP 250V 1 3HP 125 VAC 12 A Res...

Page 13: ...1000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C...

Reviews: